Date post: | 09-Mar-2023 |
Category: |
Documents |
Upload: | khangminh22 |
View: | 0 times |
Download: | 0 times |
© Copyright 2018 ABB, All rights reserved. —
DPA
250
S4
50-2
50kW
—OPER ATING MANUAL
DPA 250 S4 UPS50-250 kW 380/400/415 V IEC
2 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
—About this document
File name : 4NWD004098_OPM_ABB_DPA-S4_250_EN_REV-AUPS model : DPA 250 S4 50-250kWDate of issue : 11.12.2018Issued by : Product MarketingChecked by : R&D After SalesArticle number : N/ADocument number : 4NWD004098Revision : A
The following symbols are used in this manual, the list below describes each symbol.
— Document information
— Safety symbols and warnings
This symbol in conjunction with the signal word "DANGER" indicates an imminent electrical hazard. Failure to observe the related safety note may cause personnel injury or death or equipment damages.
This symbol in conjunction with the signal word "WARNING" indicates a potentially dangerous situation. Failure to observe the related safety note may cause personnel injury or death or equipment damages.
This symbol indicates a safety note: “ATTENTION! Hazardous voltage!”Installation by a certified service engineer only.”
This symbol in conjunction with the signal word "NOTE" indicates operator tips, particularly useful or important information for the use of the product. This symbol and wording does not indicate a dangerous situation.
This symbol indicates a compulsory action: “Reading the instruction manual/booklet before starting work or before operating equipment or machinery.
Recycle.
Do not dispose with ordinary trash.
3CO NTENTS
—Contents
1 Important safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81.1 Save these instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81.2 Safety rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122.1 Declaration of safety compliance and EC marking . . . . . . . . . . . . . . . . . . . . . . . . . . 122.2 System nameplate and identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132.3 UPS module nameplate and identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3 System description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143.1 DPA 250 S4 UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.1.1 DPA 250 S4 UPS Frame types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.1.2 UPS Frame with closed door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.1.3 DPA 250 S4 UPS Frame with open door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.1.4 General UPS Frame dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.2 DPA 250 S4 M50 UPS Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .173.2.1 UPS Module dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.3 System configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183.3.1 Standalone configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.3.2 Parallel system configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.3.3 Parallel UPS configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.4 Description of the main elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203.4.1 Single line diagram with single input feed and common batteries (default) . . . . . . . . . . 20
3.4.2 Single line diagram with dual input feed and common batteries . . . . . . . . . . . . . . . . . 21
3.4.3 Single Line Diagram with single input feed and separate batteries . . . . . . . . . . . . . . . . 22
3.4.4 Single line diagram with dual input feed and separate batteries . . . . . . . . . . . . . . . . . 23
3.4.5 Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.4.6 UPS measure, control & monitoring element description . . . . . . . . . . . . . . . . . . . . . . 26
4 Operating modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 274.1 Double conversion mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 274.2 Xtra-VFI Mode (Enhanced double conversion mode). . . . . . . . . . . . . . . . . . . . . . . . . 284.3 Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 284.4 Battery Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294.5 Maintenance bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5 Control & monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 315.1 System display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
5.1.1 Graphical display operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.1.2 Rear View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.1.3 Start up and installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.1.4 Home screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.1.4.1 Icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.1.5 Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
5.1.5.1 Mimic diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
5.1.5.2 Module selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5.1.5.3 Screen measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.1.5.4 Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.1.5.5 UPS Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.1.5.6 User . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.1.5.7 X-tra VFI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.2 Control panel UPS module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 395.2.1 Control panel elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.2.1.1 LCD display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.2.1.2 ON/OFF power button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.2.1.3 Control and navigation buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
5.2.1.4 LED status indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
5.2.2 Control panel menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
5.2.2.1 Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5.2.2.2 Events log Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5.2.2.3 Measurements Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5.2.2.4 Commands Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5.2.2.5 UPS Data Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5.2.2.6 Set Up User Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.2.2.7 Set up Service Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.3 Customer interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 435.3.1 Input dry ports (X3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
5.3.2 Output dry port (X2 and X1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
5.3.3 Network management cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
5.3.4 Smart port JD1 (Serial RS 232 / Sub D9 / Male) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
5.3.5 USB PC / Laptop Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
6 Options and accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 477 Maintenance & troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
7.1 General maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 487.1.1 User responsibilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
7.1.2 Preventive maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
7.1.3 Deep battery test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
7.1.4 Battery maintenance, disposal and recycling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
7.2 UPS disposal and recycling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 497.2.1 For professional users in the European Union . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
7.2.2 For disposal in countries outside of the European Union . . . . . . . . . . . . . . . . . . . . . . 49
7.3 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 497.3.1 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
7.3.2 Menu, commands, event log and measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
7.3.3 Fault identification and rectification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
8 Packing, transportation & storage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 548.1 Packing & transportation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 548.2 Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
8.2.1 Standard package (film) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
8.2.2 Sea freight cases (wooden box) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
8.3 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 598.3.1 UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
8.3.2 Batteries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
9 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 609.1 Environmental condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
9.1.1 Climatic conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
9.1.2 Biological conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
9.1.3 Mechanical active substance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
9.1.4 Chemical active substance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
9.1.5 Mechanical conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
9.2 UPS location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 619.2.1 Battery cabinet location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
9.2.2 Fixing of the UPS to the building structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
9.3 Electrical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 639.3.1 Single input feed - Terminals overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
9.3.2 Dual input feed - Terminals overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
9.3.3 Electrical protection and cable sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
9.3.3.1 Single input feed and common battery (default) . . . . . . . . . . . . . . . . . . . . . . 66
9.3.3.2 Single input feed and separate battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
9.3.3.3 Dual input feed and common battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
9.3.3.4 Dual input feed and separate battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
9.4 UPS connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
5
9.4.1 UPS Input connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
9.4.1.1 Mains supply and earth connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
9.4.1.2 Single input feed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
9.4.1.3 Dual input feed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
9.4.2 Output connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
9.4.2.1 Load connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
9.5 Parallel UPS connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 779.5.1 Input & output connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
9.5.2 Communication connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
9.5.3 Interface set-up and configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
10 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7810.1 Start-up procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
10.1.1 UPS parallel installation situation
10.1.2 UPS input phase rotation check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
10.1.3 Module installation and parameters check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
10.1.4 Q1 and Q2 feed-back check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
10.1.5 Modules check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80
10.1.6 Start-up procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80
10.1.7 Battery connection and check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
10.1.8 Connecting the load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
11 Shut-down procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8411.1 Complete shut-down procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
12 Maintenance bypass operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8612.1 Load transfer from inverter mode to maintenance bypass . . . . . . . . . . . . . . . . . . . . . 8612.2 Load transfer from maintenance bypass to inverter mode . . . . . . . . . . . . . . . . . . . . . 88
13 Adding/replacing a UPS module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9013.1 Single module system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
13.1.1 Remove the module from the frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90
13.1.2 Insert the module in the frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
13.2 Redundant multi-module system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9413.2.1 Remove the module from the frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
13.2.2 Insert the module in the frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
13.3 Capacity multi-module system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9713.3.1 Remove the module from the frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
13.3.2 Insert the module in the frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
14 Operation procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10114.1 Remote shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10114.2 Generator ON facility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10214.3 Xtra VFI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .103
14.3.1 Set-up mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
14.3.2 Display menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
15 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10715.1 Network interface card (SNMP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
15.1.1 CS121 basic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
15.1.2 CS121 advanced . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
15.1.3 CS121 modbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
15.1.4 Installation of the SNMP board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
15.2 Elevation kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11015.3 Battery temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
15.3.1 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .111
15.3.2 Battery temperature probe installation. . . . . . . . . . . . . . . . . . . . . . . . . . . .111
Attachments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112Technical data sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
© Copyright 2018 ABB, All rights reserved. —
DPA
250
S4
50-2
50kW
—SAFET Y INSTRUC TIONS
DPA 250 S4 UPS50-250 kW 380/400/415 V IEC
8 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
—1 Important safety instructions
This manual contains important instructions for models DPA 250 S4 that should be followed during installation and maintenance of the UPS.
It also provides guidelines to check delivery and is in- tended for people who plan the installation, installation, commission and use or service the UPS system and/or the battery cabinet. The reader is expected to know the fundamentals of electricity, wiring, electrical components and electrical schematic symbols.
READ ALL SAFETY AND OPERATING INSTRUCTIONS BEFORE OPERATING THE UPS SYSTEM. OBSERVE TO ALL WARNINGS ON THE UNIT AND IN THIS MANUAL
DANGER
• SERVICING THE UNIT SHOULD BE PERFORMED OR SUPERVISED BY PERSONNEL KNOWLEDGEABLE ABOUT BATTERIES AND REQUIRED PRECAUTIONS.
• RISK OF ELECTRIC SHOCK - THIS UNIT RECEIVES POWER FROM MORE THAN ONE SOURCE - DISCONNECTION OF AC SOURCE(S) (AND THE DC SOURCE) IS REQUIRED TO DE-ENERGIZE THIS UNIT BEFORE SERVICING
• THERE IS DANGER OF AN ELECTRICAL IMPACT.
• RISK OF EXPLOSION IF USING AN INCORRECT BATTERY TYPE.
• DO NOT EXCEED UPS AND/OR BATTERY CABINETS RATING LABELS.
• AS THE BATTERY LIFE DEPENDS ON THE ROOM TEMPERATURE, FOR THE UPS WITH INTERNAL BATTERY MODULES, AN ENVIRONMENT WITH A CLIMATE CONTROLLED SYSTEM IS RECOMMENDED IN ORDER TO MAINTAIN THE ROOM TEMPERATURE CONDITION AT 20°C
— 1.1 Save these instructions
— 1.2 Safety rules
The UPS system operates with mains, batteries or bypass power carrying high currents and volt-age. The correctly installed UPS system is grounded to earth and IP 20 rated against electric shocks and foreign objects when all dead fronts are in place. Installation and service should be carried out by the manufacturer’s qualified tech-nicians or their certified service partners.
COMMISSIONING AND OPERATIONS INSIDE THE UPS MUST BE CARRIED OUT BY A CERTIFIED SERVICE ENGINEER OF THE MANUFACTURER OR BY AN AGENT CERTIFIED BY THE MANUFACTURER.
BY NOT FULFILLING THIS OBLIGATION, THE PRODUCT MAY LOSE ITS WARRANTY
WARNING
INSTALLATION SHALL BE IN COMPLIANCE WITH ALL APPLICABLE NATIONAL, STATE, AND LOCAL CODES
Follow all operating and user instructions.
WARNING
EAD THE INFORMATION, IN ORDER TO AVOID DAMAGE TO EQUIPMENT
DANGER
KEEP OUT OF BATTERY POLES WHICH CONTAIN DANGEROUS DC-VOLTAGES CAUSING FATAL ACCIDENTS. NOTE: MANIPULATION ON THE BATTERY SYSTEM SHOULD ONLY BE DONE BY TRAINED SERVICE AND MAINTENANCE PERSONNEL OF THE MANUFACTURER OR HIS CERTIFIED SERVICE PARTNERS. INAPPROPRIATE MANIPULATIONS OF THE BATTERIES CAN CAUSE LIGHTNING SPARKS. A BATTERY CAN PRESENT A RISK OF ELECTRICAL SHOCK AND HIGH SHORT CIRCUIT CURRENT. THE FOLLOWING PRECAUTIONS SHOULD BE OBSERVED WHEN WORKING ON BATTERIES:
BEFORE READING THE OPERATING MANUAL, PLEASE CAREFULLY READ THIS CHAPTER ON IMPORTANT SAFETY INSTRUCTIONS
91 IM P O RTA NT S A FE T Y I NS TR U C TI O NS
DANGER
a. REMOVE WATCHES, RINGS OR OTHER METAL OBJECTS.
b. USE TOOLS WITH INSULATED HANDLES.
c. WEAR RUBBER GLOVES AND BOOTS.d. DO NOT LAY TOOLS OR METAL PARTS
ON TOP OF BATTERIES.e. DISCONNECT THE CHARGING SOURCE
PRIOR TO CONNECTING OR DISCONNECTING OF BATTERY TERMINALS.
f. ESTABLISH IF THE BATTERY IS INADVERTENTLY GROUNDED. IF INADVERTENTLY GROUNDED, REMOVE SOURCE FROM GROUND. CONTACT WITH ANY PART OF A GROUNDED BATTERY CAN RESULT IN ELECTRICAL SHOCK. THE LIKELIHOOD OF SUCH SHOCK CAN BE REDUCED IF SUCH GROUNDS ARE REMOVED DURING INSTALLATION AND MAINTENANCE (APPLICABLE TO EQUIPMENT AND REMOTE BATTERY SUPPLIES NOT HAVING GROUNDED SUPPLY CIRCUIT.
WARNING
THE UNIT IS HEAVY AND MAY TIP DURING TRANSPORTATION CAUSING SERIOUS INJURY IF UNPACKING INSTRUCTIONS ARE NOT CLOSELY FOLLOWED.
The only user operations permitted are:• Start up and shut down of the UPS system and/
or UPS modules (excluding the commissioning start up).
• Control of the battery circuit breaker, UPS out-put switch and Manual Bypass switch.
• Monitoring of the UPS system by the central graphical display and the UPS Module by the lo-cal control panel.
• Remote monitoring of the UPS system by SNMP, Modbus and I/O relays interfaces
The user must follow the precautions and only perform the operations described. Also in these measures the operator of the UPS System must observe the instructions in this manual. Any devi-ations from the instructions could be dangerous to the user or cause accidental load loss.
THE MANUFACTURER WILL NOT BE HELD RESPONSIBLE FOR DAMAGES CAUSED THROUGH INCORRECT MANIPULATION OF THE UPS SYSTEM.
DANGER
IT IS PROHIBITED TO REMOVE ANY PARTS FROM THE UPS SYSTEM OR FROM ANY OPTIONAL PART (E.G. BATTERY CABINET). THERE IS A DANGER OF ELECTRICAL SHOCK!
DANGER
HIGH FAULT CURRENTS (LEAKAGE CURRENTS):BEFORE CONNECTING THE MAINS YOU MUST ENSURE THAT THERE IS A PROPER EARTH CONNECTION!
DANGER
THE USER MUST DISPLAY A WARNING SHIELD ON ALL PRIMARY UPS CIRCUIT BREAKERS. THE SERVICE PERSONNEL HAS TO BE INFORMED ABOUT DANGEROUS VOLTAGES. THE WARNING PANELS MUST CONTAIN THE FOLLOWING TEXT (OR SIMILAR): “BEFORE STARTING WITH THE MAINTENANCE WORK ON THE CIRCUIT BREAKERS MAKE SURE THE UPS IS ISOLATED”.
DANGER
ALL THE INPUT/OUTPUT PORTS ARE CLASS 2 (SELV CIRCUITS). PLEASE MAINTAIN SECURITY WHEN CONNECTING TO OTHER DEVICES.
© Copyright 2018 ABB, All rights reserved. —
DPA
250
S4
50-2
50kW
—USER MANUAL
DPA 250 S4 UPS50-250 kW 380/400/415 V IEC
12 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
WARNING
THIS IS A PRODUCT FOR INDUSTRIAL APPLICATION IN THE SECOND ENVIRONMENT AS DEFINED IN IEC/EN 62040-2 CHAPTER 4 – INSTALLATION RESTRICTIONS OR ADDITIONAL MEASURES MAY BE NEEDED TO PREVENT DISTURBANCES
The UPS must be installed according to the rec-ommendations in this manual. To operate the UPS at peak efficiency, your installation site should satisfy the environmental parameters outlined in this manual. Excessive amount of dust in the op-erating environment of UPS may cause damage or lead to malfunction. The UPS should be always protected from the outside weather and sun-shine. If you intend to operate the system at an al-titude higher than 1000 meters above sea level, contact your local sales or service office for im-
portant information about high altitude opera-tion. The operating environment must meet the weight, airflow, size and clearance requirements specified in the technical datasheet.
The basic environmental requirements of the UPS system are:
Ambient Temperature Range 0 to +40˚C
Recommended Operating Range +20 to +25˚C
Maximum Relative Humidity 95% (non-condensing)
The UPS cabinet uses forced air cooling to regu-late the internal temperature of components. Air inlets are located at the front of the cabinet, and outlets at the top of the cabinet. You must allow clearance on the top of the cabinet for proper air circulation. Refer to the chapter "9.2 UPS loca-tion".
—2 General information
The product has the EC marking in compliance with the following European directives:• Low Voltage Directive: 2014/35/EC• EMC Directive: 2004/30/EC
Further ABB UPS systems are in compliance with following standards:
Product Standards Standards
Safety Standard IEC/EN 62040-1 IEC/EN 60950-1
Electromagnetic Compatibility Standard (EMC)
IEC/EN 62040-2Emission cat. C3Immunity cat. C3
IEC/EN 61000-6-2IEC/EN 61000-6-4IEC/EN 61000-4-2IEC/EN 61000-4-3IEC/EN 61000-4-4IEC/EN 61000-4-5IEC/EN 61000-4-6IEC/EN 61800-4-8
Performance Standard IEC/EN 62040-3
— 2.1 Declaration of safety compliance and EC marking
The primary function of the ABB UPS covered by the above standards is to ensure continuity of an AC power source. The UPS may also be used to improve the quality of the power source by keep-ing it within specified characteristics. The UPS has been developed over a wide range of power ranges, from 50kW to 1.25MW to satisfy require-ments for availability and quality of power to vari-ety of IT equipment and devices.
Furthermore, the ABB manufacturer is certified successfully in every area according to the model of the International Standard:ISO 9001/EN 29001. Certification of the UPS with the operating performance according to the stan-dard IEC 62040-3 and VDE 0558 Part 530 is ac-complished.
13
— 2.2 System nameplate and identification
The UPS system has a nameplate positioned on the inside of the UPS door. It contains
1 UPS product name and frame type
2 UPS electrical characteristics
3 UPS serial number
4 Production date
5 EC Marking
—2.2-1
—2.2-1: System nameplate
— 2.3 UPS module nameplate and identification
The UPS module has a nameplate positioned on the inside of the UPS module. It contains
1 UPS module name and module type
2 UPS module electrical characteristics
3 UPS module serial number
4 Production date
5 EC Marking
—2.3-1
—2.3-1: UPS module nameplate
2 G EN ER A L I N FO R M ATI O N
14 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
—3 System description
The DPA 250 S4 is a 3 ph transformer less Uninter-ruptible Power System (UPS). It is a true modular on-line double conversion UPS with a perfor-mance qualification code VFI-SS-111 providing quality power for sensitive equipment.
It is a modular UPS system consisting of:• DPA 250 S4 UPS Frame, max rated power of
250kW (N+1)
• Up to 6 x DPA 250 S4 UPS modules, rated power 50 kW
• Bottom/Top cable entry including incoming / outgoing and battery terminals
• Maintenance bypass switch (optional)• System graphical display (optional)• Parallel kit and cable (5mt) (optional)• Communication interfaces
— 3.1 DPA 250 S4 UPS
The DPA 250 S4 frame has 6 configuration as follow:
Description Configuration
Bottom cable entry (BCE)
UPS DPA 250 S4 F250-6 BCE SPVersion with built-in MBS available
UPS frame is equipped with system graphical display, par-allel kit and cable, up to 6 x UPS Module slots (N+1).Suitable for parallel system configuration.
UPS DPA 250 S4 F250-6 BCE PVersion with built-in MBS available
UPS frame is equipped with parallel kit and cable, up to 6 x UPS Module slots (N+1).Suitable for parallel system configuration.
UPS DPA 250 S4 F250-6 BCE S MBS UPS frame is equipped with system graphical display, main-tenance bypass switch (MBS), up to 6 x UPS Module slots (N+1). Suitable for standalone configuration.
Top cable entry (TCE)
UPS DPA 250 S4 F250-6 TCE SPVersion with built-in MBS available
UPS frame is equipped with system graphical display, par-allel kit and cable, up to 6 x UPS Module slots (N+1).Suitable for parallel system configuration.
UPS DPA 250 S4 F250-6 TCE PVersion with built-in MBS available
UPS frame is equipped with parallel kit and cable, up to 6 x UPS Module slots (N+1).Suitable for parallel system configuration.
UPS DPA 250 S4 F250-6 TCE S MBS UPS frame is equipped with system graphical display, main-tenance bypass switch (MBS), up to 6 x UPS Module slots (N+1).Suitable for standalone configuration.
3.1.1 DPA 250 S4 UPS Frame types
1515
3.1.2 UPS Frame with closed door
3 S YS TEM D E SCR IP TI O N
With display, applicable for: Without display, applicable for:
UPS DPA 250 S4 F250-6 BCE SPUPS DPA 250 S4 F250-6 BCE S MBSUPS DPA 250 S4 F250-6 TCE SPUPS DPA 250 S4 F250-6 TCE S MBS
UPS DPA 250 S4 F250-6 BCE PUPS DPA 250 S4 F250-6 TCE P
16 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
3.1.3 DPA 250 S4 UPS Frame with open door
Bottom cable entry Top cable entry
3.1.4 General UPS Frame dimensions
Model DPA 250 S4
Dimensions (WxHxD) mm 795 x 1978 x 943
17173 S YS TEM D E SCR IP TI O N
The UPS module of the DPA 250 S4 is the core engine of this modern, high quality UPS. The module includes all essential parts of a complete double conversion UPS: Rectifier, inverter, DC-converter (battery charger), static bypass switch and back feed protection. Each module has also its own control logic and small display
— 3.2 DPA 250 S4 M50 UPS Module
for monitoring and management. This allows for the modules to be completely independent and act fully redundant with each other. Decentral-ized paralleling architecture (DPA™) is the most reliable modular architecture – as if having indi-vidual UPS connected in parallel, but in a single frame.
3.2.1 UPS Module dimensions
Rated power 50kW
Ingress of protection IP20
Weight 66 kg
Dimensions (WxHxD) 706 x 175 x 825
WARNING
DANGER
THE FOLLOWING LABELS ARE PLACED ON THE UPS MODULE:
18 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
— 3.3 System configuration
3.3.1 Standalone configuration
3.3.2 Parallel system configuration
The DPA 250 S4 250 kW frame can be equipped with up to 6 modules (N+1 configuration). In the tablebelow, standard configurations are listed and described.
Number of modules
1 x 50 kW 2 x 50 kW 3 x 50 kW 4 x 50 kW 5 x 50 kW 6 x 50 kW
Maximum load
50 kW 100 kW 150 kW 200 kW 250 kW 250 kW
Configuration with maximum load
N+0 N+0 N+0 N+0 N+0 N+1
Note: Depending on the actual load level system features automatically redundancy.
The DPA 250 S4 UPS unit can be paralleled to increase the power capacity up to 1500kW. Up to 6 UPS units with 30 UPS modules can be configured as shown in the table below:
Number of UPS units
1 x 250 kW 2 x 250 kW 3 x 250 kW 4 x 250 kW 5 x 250 kW 6 x 250 kW
Maximum load
250 kW 500 kW 750 kW 1000 kW 1250 kW 1500 kW
Maximum number of UPS Modules
6 12 18 23 29 30
Configuration with maximum load per frame
N+1 N+1 N+1 N+1 N+1 N+0
Note: Depending on the actual load level system features automatically redundancy.
19
ONLY PEOPLE WHICH HAVE BEEN TRAINED BY SERVICE TECHNICIANS OF THE MANUFACTURER OR HIS CERTIFIED SERVICE PARTNERS ARE ALLOWED TO START UP AND COMMISSIONING THE UPS SYSTEM.
The control and monitoring communication for the parallel UPS units are secured by using aring-bus communication. The ring-bus technique loops back the parallel communication cable from the last frame in the system. This introduces an alternative communication path in case one cable in between two UPS units is disconnected for whatever reason.
—3.3.3-1
—3.3.3-1: Ring communication for parallel UPS units
3.3.3 Parallel UPS configuration
The UPS system consisting of parallel UPS units requires:• Master UPS unit equipped with system graphical display, N x UPS modules (N > 0 and < 6) and
parallel cable kit (5 mts). • N parallel UPS unit equipped with parallel cable kit (N < 6)
FRAME 1 FRAME 2 … FRAME 5 FRAME 6
System graphical display •Parallel Cable Kit • • • •
3 S YS TEM D E SCR IP TI O N
20 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
— 3.4 Description of the main elements
The UPS has single input feed and common battery connections. These are provided by a common in-put feed busbar and a common battery busbar.
3.4.1 Single line diagram with single input feed and common batteries (default)
—3.4.1-1
—3.4.1-1: Single line diagram with single input feed and common batteries (default)
21
Applicable for dual input feed and common batteries. The common input feed busbar should be re-moved.
3.4.2 Single line diagram with dual input feed and common batteries
—3.4.2-1
—3.4.2-1: Single line diagram with dual input feed and common batteries
3 S YS TEM D E SCR IP TI O N
22 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
Applicable for single input feed and separate batteries. The common battery busbar should be re-moved.
3.4.3 Single Line Diagram with single input feed and separate batteries
—3.4.3-1
—3.4.3-1: Single Line Diagram with single input feed and separate batteries
233 S YS TEM D E SCR IP TI O N
Applicable for dual input feed and separate batteries. The common input feed and battery busbars should be removed.
3.4.4 Single line diagram with dual input feed and separate batteries
—3.4.4-1
—3.4.4-1: Single line diagram with dual input feed and separate batteries
24 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
Section Component Functional Description
Main input terminals (X3)
X3.1 Rectifier input terminal, phase 1Provides a connection be-tween the utility supply and the rectifier input
X3.2 Rectifier input terminal, phase 2
X3.3 Rectifier input terminal, phase 3
X6 - N Neutral terminal
X7 - PE Ground (earth) terminal
Bypass input terminals (X4)
X4.1 Bypass input terminal, phase 1Provides a connection be-tween the bypass supply and UPS bypass input
X4.2 Bypass input terminal, phase 2
X4.3 Bypass input terminal, phase 3
X6 - N Neutral terminal
System output terminals (X2)
X2.1 System output terminal, phase 1Provide a connection be-tween the UPS system and the load
X2.2 System output terminal, phase 2
X2.3 System output terminal, phase 3
X6 - N Neutral terminal
X7 – PE Ground (earth) terminal
Battery terminals (X5)
X501.1 Positive pole (+) of the battery terminal UPS Module 1
Provides a connection be-tween the external battery and the UPS system.
X502.1 Positive pole (+) of the battery terminal UPS Module 2
X503.1 Positive pole (+) of the battery terminal UPS Module 3
X504.1 Positive pole (+) of the battery terminal UPS Module 4
X505.1 Positive pole (+) of the battery terminal UPS Module 5
X506.1 Positive pole (+) of the battery terminal UPS Module 6
X501.2 Negative pole (-) of the battery terminal UPS Module 1
X502.2 Negative pole (-) of the battery terminal UPS Module 2
X503.2 Negative pole (-) of the battery terminal UPS Module 3
X504.2 Negative pole (-) of the battery terminal UPS Module 4
X505.2 Negative pole (-) of the battery terminal UPS Module 5
X506.2 Negative pole (-) of the battery terminal UPS Module 6
Battery circuit breaker (Q5)
Q501 Battery circuit breaker UPS module 1, 2P
Battery over current pro-tective device (MCB).
Q502 Battery circuit breaker UPS module 2, 2P
Q503 Battery circuit breaker UPS module 3, 2P
Q504 Battery circuit breaker UPS module 4, 2P
Q505 Battery circuit breaker UPS module 5, 2P
Q506 Battery circuit breaker UPS modules 6, 2P
3.4.5 Functional description
253 S YS TEM D E SCR IP TI O N
Maintenance bypass switch (Q1)
Q1 Maintenance bypass switch (MBS)
The manual bypass switch connects the load direct to the bypass input supply when it is closed (ON). The UPS is isolated for ser-vices or maintenance work.
UPS Power Modules (Ax)
A1 UPS module 1
The UPS module has a rated power of 50 kW. It has a decentralized paral-lel architecture (DPA) as described in chapter 3.2
A2 UPS module 2
A3 UPS module 3
A4 UPS module 4
A5 UPS module 5
A6 UPS module 6
Output UPS switch (Q2)
Q2 UPS output switch
Allows to isolate an UPS Frame and built-in UPS modules from the load. Es-pecially useful when swap-ping modules or inserting new modules into the sys-tem because with the switch open it is possible to power the modules, configure it and perform functional tests before connecting it to the rest of the system and to the load.
26 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
3.4.6 UPS measure, control & monitoring element description
—3.4.6-1
—3.4.6-1: UPS measure, control & monitor-ing elements
Ref DES Component Functional description
A40 Parallel board
• Provides communication between the UPS modules to monitor operating status and load sharing.
• Provides a Sync port to synchronize the UPS output with an external sources.
For details refer to chapter "5 Control & Monitoring"
A60 Interface board
• Acquires the status of the output and maintenance bypass switches
• Acquires the battery temperature value • Provides 5 digital inputs and 5 output relays• Provides RS232 interface and USB port to monitor
the UPS by using the Wavemon software
For details refer to chapter "5 Control & Monitoring"
A65UPS Network management card (NMC) (optional)
The UPS network management card provides remote monitoring via web by using SNMP, Modbus RS-485 and Modbus TCP/IP
For details refer to chapter "5 Control & Monitoring"
A61 DPA 250 S4 HMI (optional)The touchscreen graphical display allows the operator to control and monitor the UPS system.
For details refer to chapter "5 Control & Monitoring"
27
—4 Operating modes
In double the conversion mode, the load is connected to the UPS Inverter (INV) and the Rectifier is sup-plied by the main utility supply (L1). The battery remains charged or is under charged. The double con-version mode protect the load from any utility main disturbance or failure.
— 4.1 Double conversion mode
—4.1-1
—4.1-1: “Double conver-sion” operating mode
When the UPS system is in a double conversion mode, the status of UPS module control panel is dis-played as follow:
LED Indicator Color
Rectifier Green
Bypass Green
Battery Green
Output Green
Breaker Status
MBS (Q1) Open
UPS Output switch (Q2) Closed
—4.1-2
—4.1-2: “Inverter Mode” control panel mimic
In the unlikely event of an inverter fault or overload condition the UPS will transfer the load - automati-cally and without interruption to the static bypass (transfer time = 0).
4 O PER ATI N G M O D E S
28 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
In Xtra-VFI Mode, the UPS system adapts the power capacity according to the partial AC load by put-ting the unused UPS module in stand-by mode. The remaining UPS modules are operating in double conversion mode. The UPS system autonomously decides which UPS module goes into stand-by mode. The system shall rotate/swap the UPS modules between the double conversion mode and the stand-by mode to extend the operating life and equalize aging.The status of the UPS Module in Xtra-VFI Mode is displayed as follow:
— 4.2 Xtra-VFI Mode (Enhanced double conversion mode)
LED Indicator Color
Rectifier Green
Bypass Green
Battery Green
Output Blue
Breaker Status
MBS (Q1) Open
UPS Output switch (Q2) Closed
—4.2-1
—4.2.1: “Standby Mode” control panel mimic
In Bypass Mode, the load is supplied from the bypass mains (L2) through the static bypass . The Inverter is OFF.
— 4.3 Bypass Mode —4.3.1: “OFF LINE” operating mode
—4.3-1
In the Bypass Mode the battery charger remains active. In the event of a bypass mains (Line 2) failure, the load will automatically be transferred from the mains to the inverter within 5 ms (this is valid for single and parallel systems). If the Utility Mains supply (LINE 1) is not available, the energy is supplied by the battery.
29
When the UPS system is in bypass mode, the status of UPS module control panel is displayed as follow :
LED Indicator Color
Rectifier Green
Bypass Green
Battery Green
Output Yellow
Breaker Status
MBS (Q1) Open
UPS Output switch (Q2) Closed
—4.3-2
—4.3-2: “Bypass Mode” control panel mimic
The "Bypass-Mode”, is recommended only if the loads can tolerate interruptions of 3-5 ms (trans-fer time from the Bypass Mode to the Double Conversion Mode). NOTE
TO REACH THE HIGHEST ESSENTIAL SECURITY LEVEL, WE RECOMMEND RUNNING OF THE UPS ON NORMAL OPERATION MODE, THEREFORE THE UPS MODE (MODE "ON-LINE”)
In Battery Mode, the load is connected to the inverter (INV) and the inverter is supplied by the battery or the energy storage system. The utility main supply is not available (L1).
— 4.4 Battery Mode
—4.4-1
—4.4-1: “ON BATTERY” operating mode
When the UPS system is in battery mode, the status of UPS module control panel is displayed as follow :
LED Indicator Color
Rectifier Red
Bypass Green
Battery Green
Output Green
Breaker Status
MBS (Q1) Open
UPS Output switch (Q2) Closed
—4.4-2
—4.4-2: “Battery Mode” control panel mimic
4 O PER ATI N G M O D E S
30 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
The Maintenance Bypass Mode is performed by means of the Q1 MANUAL BYPASS SWITCH.
POSITION OF SWITCH EFFECT
ON Bypass-Switch Closed (Load supplied directly from bypass mains)
—4.5-1
POSITION OF SWITCH EFFECT
OFF Bypass-Switch Open – Normal operating condition(Load supplied by inverter)
—4.5-2
— 4.5 Maintenance bypass—4.5.1: “Maintenance bypass switch closed” operating mode
NOTE
TO HAVE TO MOST ESSENTIAL SECURITY LEVEL, WE RECOMMEND TO RUN THE UPS ON NORMAL OPERATION MODE, MEANS UPS MODE (MODE "ON-LINE”)
Once the critical load is feed by the bypass mains, the UPS module can be isolated for maintenance or testing
—4.5.2: “Maintenance bypass switch opened” operating mode
31
—5 Control & monitoring
ONLY NLY PEOPLE TRAINED BY SERVICE TECHNICIANS OF THE MANUFACTURER OR HIS CERTIFIED SERVICE PARTNERS ARE ALLOWED TO OPERATE ON THE CONTROL PANEL WITH CLOSED DOORS.ALL OTHER INTERVENTION ON THE UPS SYSTEM SHOULD ONLY BE CARRIED OUT BY SERVICE TECHNICIANS OF THE MANUFACTURER
The user-friendly, touch screen graphical display on the system level offers the opportunity of di-rect monitoring the system status as well as the status of each individual UPS module. The graphi-cal display additionally provides all of the mea-
— 5.1 System display—5.1-1: System display
surements (module and system level) and the user is able to transfer from double conversion to bypass mode and vice-versa. All other commands must be performed on the local UPS module con-trol panel. With both displays in place (module and system level), the UPS offers full user friendli-ness without compromising rigidity.The system display is also equipped with an alarm indication bar that shows the main status of the UPS system. If the unit is in normal condition mode, a green light will be on; if an alarm occurs on the unit, a yellow light will be on and if the unit is in fault condition, a red light will be on.
—5.1-1
5.1.1 Graphical display operation
For simple operation and configuration, the UPS is optionally delivered with a microprocessorbased touch screen display. The navigation, pro-cedures and the features of the display are de- tailed in subsequent sections.
The touch screen display enables the operator to perform the following:
• Check operational status and measurements• Execute operational commands
(PASSWORD PROTECTED)• Monitor the power flow through the UPS system • Check events and alarm history• Silence alarms• Adjust programmable parameters• Check the status of the batteries
5 CO NTR O L & M O N ITO R I N G
32 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
5.1.2 Rear View
NOTE
PLEASE NOTE THAT THE EMERGENCY SHUTDOWN FUNCTION BY PRESSING THE BUTTONS ON/OFF 1 + ON/OFF 2 IS DISABLED
—5.1.2-1: Rear view
—5.1.2-1
I/O PORTS
SD Card Slot for the SD card
USB USB connector
DC Input Power supply connector (only needed if the RJ-45 cable is >75 & <100m)
UPS Input RJ-45 connector
LED’s
UPS StatusGREEN: when the UPS is on inverter mode RED: when the inverter is on alarm
AlarmOFF: if no alarm present RED: if unread alarm(s) present
BUTTONS
Reset Press the “Reset” button to reset the remote panel
ON/OFF 1/2Press “ON/OFF 1” + “ON/OFF 2”: Function disabled Press “Reset” + “ON/OFF 1” buttons simultaneously, then release "Reset" and hold the "ON/OFF 1" button for 10 seconds: Touch screen calibration
5.1.3 Start up and installation
When the UPS is energized, the display automatically turns on. It is initiated for a few seconds and sub-sequently the user is directed to the mimic diagram screen.
335 CO NTR O L & M O N ITO R I N G
5.1.4 Home screen
The display is driven by a menu-prompted software. The home screen is accessible from any screen and gives access to the following:
—5.1.4-1: Rear view
—5.1.4-1
A B
C D
5.1.4.1 Icons
Icon View Description
A Date day - month - year
B Time hours : minutes: seconds
C System statusSystem status: indicates that the user is in the system level naviga-tion.
D UPS number*The numbering after the symbol „P” is sequential and represents each module or frame in the system. For eg. “P01” indicates the UPS number 01 in a parallel system.
HomeThe Home button is accessible from all screens and directs to the Home screen, the main screen of the display.
Mimic DiagramThe mimic diagram button is accessible from all screens and directs to the Mimic diagram (system level) screen.
Xtra VFIThe Extra VFI button is accessible from all screens and function as toggle to switch between Xtra VFI measures screen and Xtra VFI sta-tus bar screen.
WarningThis symbol appears in case of alarms or events on any screen. Touching this icon the alarm is silenced and directs to the Event log screen.
Modules selectionDirects to the Module selection screen from where it is possible to select the module and start the navigation (status and measure-ments) on module level.
34 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
Event logDirects the user to the Event log screen where the stored events and alarms are shown in chronological order.
MeasuresThis button directs to the Measures screen which displays electrical measurements of the UPS such as voltages, power, currents, auton-omy, etc. Not Needed for XTRA VFI.
CommandPASSWORD NEEDED : enables the operator to execute the following basic operations: “Load to inverter”, “Load to bypass”.
UPS DataDirects to the UPS data screen which gives information regarding the identity of the UPS.
UserThis button directs to the User settings sub-menu allows to set time and date, language, etc.
ServicePASSWORD NEEDED : enables the service technician to perform re-stricted commands, enable or disable Xtra VFI and set restricted UPS parameters.
1
2
1The password for accessing the command menu is different than the one needed to access the service menu
2The password for accessing the service menu is different than the one needed to ac-cess the command menu
5.1.5 Navigation
The mimic diagram is the default screen. It shows the power flow through the UPS system (standalone as well as parallel configuration) and indicates its status. This diagram can be accessed from any screen using the corresponding icon in the display header.
The interactive blocks in the mimic diagram are the following:
5.1.5.1 Mimic diagram
—5.1.5.1-1
STATICBYPASS
RECTIFIER
INVERTER
BATTERY
The green connecting lines indicate the power flow in the system
35
The color of each block identifies its functional status. There are four main colors in the mimic diagram:• Green: In operation• White: Inactive block• Yellow: Warning condition• Red: Fault condition
Device Color meaning
Rectifier Green: Rectifier is on.Red: Rectifier is switched off.
Inverter Green: Load is on inverter.Red: Inverter is switched off.
Bypass Green: Load is on bypass White: Bypass is switched off.
Battery Green: Battery is charging or discharging.Yellow: Battery is low.Red: Battery is in fault condition or is discharged.
Arrows indicate if battery is charging or discharging.
Maintenance Bypass Q1 Yellow: Load is on maintenance bypassWhite: Maintenance bypass opened
Output Breaker Q2 Green: UPS output breaker is closed (Position ON) Red: UPS output breaker is opened (Position OFF)
Touching the functional blocks in the mimic diagram, the measurements related to the object selected are displayed.
5.1.5.2 Module selection
By pressing the icon Module selection, the user starts the navigation (status and measure-ments) on the UPS module level. The module selection screen will show the amount of UPS modules in the system and the status as follows:
Active. The UPS module is running in double conversion,bypass or battery mode.
Standby. The UPS module is in standby mode (inverter OFF).
Alarm. UPS module with general alarm.
Module switched OFF (load-OFF), but physically present in the frame. (If a module is not physically present in the frame, no icon appears).
5 CO NTR O L & M O N ITO R I N G
36 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
Example with 5 modules all in operation. Example with 20 modules all in operation.
Example with 5 modules, 01-03 in operation, 04 switched OFF (load-OFF), and 05 with general
alarm.
Example with 30 modules all in operation.
Mimic diagram UPS Module
By touching one of the UPS Module icons the user gains access to the UPS module level. The mimic diagram of the selected module will appear. From this point navigation allows for access to spe-cific measurements and checking of the status of the selected module.
—5.1.5.2-1: Mimic diagram screen of a UPS module which is “active”
—5.1.5.2-1
—5.1.5.2-2: Mimic diagram screen of a UPS module which is “standby”
—5.1.5.2-2
37
UPS MEASUREMENTS BATTERY XTRA VFI
Output Voltage (V)Output Current (A)Output Frequency (Hz)Output Power (%)Active Power (kW)Reactive Power (kVAr)Apparent Power (kVA)Bypass Voltage (V)Bypass Frequency (Hz)Rectifier Voltage (V)Bypass Temperature (°C)
Temperature (°C)Discharge Current (A)Charge Current (A)Voltage (V)Run TimeCapacity(%)
StatusInverters onInverters in standbyTotal saved energy [kWh]Saved energy [kWh]Reset saved energy counter
5.1.5.3 Screen measurements
COMMAND
Load to inverterLoad to bypass
5.1.5.4 Commands
This menu provides access to information regarding manufacturing of the UPS frame.
UPS DATA
Serial NumberManufacturingDisplay VersionText version
5.1.5.5 UPS Data
This menu allows the user to program battery tests and to configure operations using gen- erators. It also allows to set the time and date and the selection of the language of the display.
USER SETTINGS
LanguageDisplay calibrationDisplay contrastMute touch sound
5.1.5.6 User
5 CO NTR O L & M O N ITO R I N G
38 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
By touching the Xtra VFI icon, the user acquires access to the Xtra-VFI settings. The Xtra VFI mode al-lows turning into standby mode of a certain number of UPS modules according to the required power capacity by the AC load.
The following conditions shall be considered before the Xtra-VFI function is activated:
• The UPS system is operating in double conversion mode.• The UPS output switch (Q2) is closed• The total number of UPS Modules inserted into the UPS system is equal to the total number of UPS
Modules in the system• There is no active alarm within the system • The battery test is not active
Xtra VFI Statuses
Xtra VFI can assume the statuses listed and described in the following table. The current status is shown on the display on the screen Xtra VFI measurements (see figure 11.3.2-2 in the chapter 11.3.2).
MESSAGE MEANING
“Disabled” Xtra VFI is disabled (factory default).
“Active” Xtra VFI is active.
“Rotation” Module rotation in progress.
"To standby" One or more modules are changing status from double-conver-sion into standby mode.
“Sysmod invalid” The “Total UPS Number” parameter has not been inserted.
“Sysmod wrong” The “Total UPS Number” parameter does not correspond with the quantity of the UPS modules in the system.
“General alarm” Any alarm on any of the modules generates the general alarm.
"Q2 open” One or more UPS output switch(es) are OPEN.
“Battery test" One or more modules are performing the battery test
Standby modeWhen the UPS module goes into the standby mode it turns off the inverter, in order to reduce power consumption. The control logic as well as the rectifier and battery charger remains active. The UPS module in Stand-by mode needs 40-50 ms to turn on the inverter and operate in double-conversion mode if the system requires it.
Module rotationModule rotation allows to keep the aging of the modules more or less balanced over time. The module rotation will take place automatically, once a week, exactly 24*7 hours after the last time Xtra VFI has been started (enabled) and it works in the following way: there is a form of intelligence that determines how many UPS modules it is worth swapping. Once this is defined, the system turns ON (change status from Standby mode to double conversion mode) the defined quantity of UPS modules first; then, once those are in a steady state, it puts the same quantity of the UPS modules which were previously in dou-ble conversion in the standby mode.
ONLY PEOPLE WHICH HAVE BEEN TRAINED BY SERVICE TECHNICIANS OF THE MANUFACTURER OR HIS CERTIFIED SERVICE PARTNERS ARE ALLOWED TO ACTIVE OR DISABLE THE XTRA-VFI MODE IN THE UPS SYSTEM.
5.1.5.7 X-tra VFI
39
32
1
DISPLAY
ON/OFF
OUTPUT LED
ALARM LED
BYPASS LED
RECTFIER LED
BATTERY LED
CONTROL BUTTONS
The DPA 250 S4 UPS module has a control panel consisting of:
• LCD display • Power ON/OFF button• Control and navigation buttons• Led status indicators
— 5.2 Control panel UPS module
—5.2-1: UPS module control panel
ONLY PEOPLE WHICH HAVE BEENTRAINED BY SERVICE TECHNICIANS OF THE MANUFACTURER OR HIS CERTIFIED SERVICE PARTNERS ARE ALLOWED TO OPERATE ON THE CONTROL PANEL WITH CLOSED DOORS.ALL OTHER INTERVENTION ON THE UPS SYSTEM SHOULD ONLY BE CARRIED OUT BY SERVICE TECHNICIANS OF THE MANUFACTURER
—5.2-1
5.2.1 Control panel elements
The display has three sections:
1. Mimic diagram of the UPS module showing the rectifier, battery, static bypass, inverter status and the input, bypass, battery and output measurements : voltage, frequency, power
2. UPS module status: module off, module dis-connected, inverter mode, bypass mode, bat-tery mode, stand-by mode
5.2.1.1 LCD display
—5.2.1.1-1
—5.2.1.1-1: Control panel elements
3. UPS module location : UPS frame and module number
The LCD display goes into “Screensaver mode” by turning the screen off after 5 minutes if the control panel is not in use. The screensaver mode is deactivated if any control button is pressed or alarm popup.
By pressing the ON/OFF button
• Start up : the UPS Module turns ON by starting the normal operations and going into the “On-line” mode if main input is applied. The LCD display shows “Load on inverter”
• Shut-down : the UPS Module turns OFF if the button is pressed for 3 seconds and the user confirms the shut-down.
5.2.1.2 ON/OFF power button
5 CO NTR O L & M O N ITO R I N G
40 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
The control and navigation buttons allow the user to perform settings and adjustments, monitor the voltages, currents, frequencies, power measurements and scroll the main and sub-menus in the UPS module.
BUTTON FUNCTION
By pressing UP button• Scroll up the sub-menu or setting/parameter• When performing a setting/adjustment increase the value or parameter
By pressing DOWN button• Scroll down the sub-menu or setting/parameter• When performing a setting/adjustment decrease the value or parameter
By pressing BACK button• Scroll back to top level menu.• Cancel any setting/parameter and back to the previous value• Cancel the audible alarm emitted by the buzzer
By pressing ENTER button• Enter into the selected sub-menu• When performing a setting/parameter confirm and enter the value
After the start-up of the UPS module, by pressing any button, the Main menu is displayed.
5.2.1.3 Control and navigation buttons
The user is able to identify the status of the bypass, rectifier, battery and UPS output and the alarm by reading the LED indicators. The LEDs are always active even if the display is in screensaver mode.
BYPASS LED (L2)• Green: bypass mains is available• Red: bypass main is not available or out of voltage/frequency toler-
ance
RECTIFIER LED (L1)• Green: rectifier mains is available• Red: rectifier mains is not available or out of voltage/frequency toler-
ance
BATTERY LED
• Green: the battery is connected and charged• Flashing green: battery mode or battery test is performed• Red : battery failure, battery voltage/temperature high or performed
battery test is not ok• Flashing red : battery is not detected or disconnected • Yellow : battery low/discharged
OUTPUT LED
• Green : UPS module output is available and supplied by the inverter• Yellow: UPS module output is available and supplied by the STATIC
bypass• Blue: UPS module is in Standby Mode (XTRA-VFI)• Non lighted: Load OFF or Q2 open
ALARM LED• Non lighted: no events/alarms pending • Yellow: events pending • Red: common alarm
5.2.1.4 LED status indicators
41
5.2.2 Control panel menus
5.2.2.1 Main Menu
5.2.2.2 Events log Menu
5.2.2.3 Measurements Menu
5.2.2.4 Commands Menu
5.2.2.5 UPS Data Menu
5 CO NTR O L & M O N ITO R I N G
42 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
5.2.2.6 Set Up User Menu
5.2.2.7 Setup Service Menu
ONLY PEOPLE WHICH HAVE BEEN TRAINED BY SERVICE TECHNICIANS OF THE MANUFACTURER OR HIS CERTIFIED SERVICE PARTNERS ARE ALLOWED TO ACCESS THE SETUP SERVICE MENU
43
• Each UPS unit is supplied with the customer interface ports which provide information about the UPS system as follow:
—5.3-1
1 Slot 1/2Slot for optional Modem / Ethernet card and SNMP Card
2 JD1RS232 Sub D9 / female PC / laptop connection
3 SD card Slot for Secure Digital (SD) cards
4 USB PC / laptop connection
5 J3 Graphical display connection
6 S1DIP-SWITCH for customer interface configuration (see chapters 3.3 and 9.5)
7 J2(RJ 45) Multi-drop connection(multi-cabinet configuration)
8 X3 UPS inputs and 12VDC source (X3 5/6)
9 X2UPS outputs dry ports (potential free contacts)
10 X1Interlock Function (External maintenance bypass switch)
11 X1 sync
Sync input: Allows for synchronization of the output of a UPS system (single UPS or parallel sys-tem) with another UPS system, another electrical equipment (AC) or an external grid. See Service Manual. Optional Syn-chronization Feature is required
12 SW1DIP-SWITCH for parallel UPS configuration (see chapters 3.3 and 9.5)
13 JD1 Input parallel BUS connector
14 JD2 Output parallel BUS connector
— 5.3 Customer interface
—5.3-1: Customer interface
5 CO NTR O L & M O N ITO R I N G
44 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
5.3.1 Input dry ports (X3)
The UPS is equipped with digital input and output relays located in the UPS frame. The I/O are located as follow:
• X1-X3 can hold Cable from 0.2mm2 – 1.5mm2• All X3 (except X3 5/6 which is a 12VDC source) are inputs, cable max. R 50Ω at 20mA
Block Terminal Contact Signal On Display Function
X3
X3 / 14GND
IN
GND Battery Temperature(Only the optional battery sen-sor from ABB is compatible)X3 / 13 +3.3VDC
X3 / 12GND
IN
GNDGENERATOR_
OPER_ONGenerator Operation(N.O.) Min. contact load 12V / 1mA
X3 / 11 +12Vdc
X3 / 10GND
IN
GNDPARRALEL_SW_OPEN
PARRALEL_SW_CLOSE External Output Breaker (N.O.) Min. contact load 12V / 20mA.
X3 / 9 +12Vdc
X3 / 8GND
IN
GND
EXT_MAN_BYP External Manual Bypass (N.O.) Min. contact load 20mA
X3 / 7 +12Vdc
X3 / 612V
GND
+12Vdc+ 12 VDC source (UPS protected) (Max. 200mA)
X3 / 5 GND
X3 / 4GND
IN
GNDREMOTE_
SHUTDOWN
RSD (Remote Shut down)Default setting: disabled. Possibility to enable and set NO or NC via NewSet.X3 / 3 +12Vdc
X3 / 2C
NO
-REMOTE_
SHUTDOWN
RSD (Remote Shut down ) for external switchMax. 250Vac/8A ;30Vdc/8A; 110Vdc/0.3A ;220Vdc/0.12A X3 / 1 -
45
Block Terminal Contact Signal On Display Function
X2
X2 / 18
CNCNO
- Common
X2 / 17 -Relays AUX(Function on request, to be defined)
X2 / 16 -
X2 / 15
CNCNO
COMMON_ALARM Common
X2 / 14 ALARM No Alarm Condition
X2 / 13 Common Alarm (System)
X2 / 12
CNCNO
LOAD_ON_MAINS Common
X2 / 11 Message No Load on Bypass
X2 / 10 Load On Bypass (Mains)
X2 / 9
CNCNO
BATT_LOW Common
X2 / 8 ALARM Battery Ok
X2 / 7 Battery Low
X2 / 6
CNCNO
LOAD_ON_INV Common
X2 / 5 Message No Load on Inverter
X2 / 4 Load on Inverter
X2 / 3
CNCNO
MAINS_OK Common
X2 / 2 ALARM Mains Failure
X2 / 1 Mains Present
X1
X1 / 2 -
EXT_MAN_BYPInterlock FunctionMax. 30Vdc/2A; 60Vdc/0.7A(Ext Manual Bypass) / 2ATX1 / 1 -
5.3.2 Output dry port (X2 and X1)
X2 terminals can hold Cable from 0.2mm2 – 1.5mm2X2 are potential free contacts and are rated: Max 250Vac/8A; 30Vdc/8A; 220Vdc/0.12A
5 CO NTR O L & M O N ITO R I N G
46 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
—5.3.3-1: CS141 BasicSupport SNMP and Modbus TCP/IP protocols
—5.3.3-2
—5.3.3-2: CS141 AdvancedSupport SNMP, Modbus TCP/IP and Peripheral options
5.3.4 Smart port JD1 (Serial RS 232 / Sub D9 / Male)
The smart port JD1 located on the customer interface board is a RS 232 serial port. It is D-type connec-tor, 9-pin male. The RS232 interface allows the user to connect the UPS unit to a computer and monitor the UPS status by using the Wavemon software. Further it is used to download system event log and make firmware upgrades.
The figure 5.3.4-1 shows how to connect a PC to the UPS with different Sub-D connectors.
—5.3.4-1
—5.3.4-1: Connector Cable - PC Serial Port with 9-Pin Connection
5.3.5 USB PC / Laptop Interface
The Computer Interface USB has the same function as the RS 232 serial port JD1. Use either USB or RS232 but not both at the same time.
5.3.3 Network management cards
The UPS can be equipped with Network inter- faces cards allowing for the connection of the UPS to the digital control system, SCADA, EDS system by SNMP, Modbus RS-485 and Modbus TCP/IP protocols.
The network management cards offers:• Real-time monitoring of the status of the UPS
system via web• Event log records in a log file• Safety remote shutdown of the UPS
—5.3.3-3
—5.3.3-1
—5.3.3-3: CS141 ModbusSupport SNMP, Modbus TCP/IP and ModBus RS485
47
—6 Options and accessories
ARTICLE DESCRIPTION DETAIL
Product options or features – electronics & software
00-6022 Parallel cable kit 10m
00-8685 Parallel cable kit 15m
00-8686 Parallel cable kit 20m
00-8687 Parallel cable kit 25m
4NWP104095R0004 Elevation kit
Product options or features – external batteries
00-3563 Temperature probe for batteries Cable length 1.3m.
Packaging
4NWP103846R0001 Carton packaging for one DPA 250 S4 module
4NWP101978R0001 Light sea freight packaging DPA 250 S4 frame
4NWP101978R0001 Sea freight packaging DPA 250 S4 frame
Documentation
00-2976 Certificate of origin Legalized invoice is also available.
04-0160 Duplicate of the commissioning report
04-0161 Duplicate of archived commissioning rep.
Other
4NWP104096R0001 12 months extra warranty for 1 DPA 250 S4 module
Available for 50kW modules
6 O P TI O NS A N D ACCE SSO R I E S
48 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
—7 Maintenance & troubleshooting
THE OPERATIONS DESCRIBED IN THIS CHAPTER MUST BE PERFORMED BY A CERTIFIED SERVICE ENGINEER OF THE MANUFACTURER OR BY AN AGENT CERTIFIED BY THE MANUFACTURER
7.1.1 User responsibilitiesThe user is not allowed to carry out maintenance on the UPS, we recommend that you contact local certified service engineers.
7.1.2 Preventive maintenanceThe UPS system needs regular and constant maintenance (preventive inspections) at least once a year, even during the warranty period.
Please refer to your authorized service partner for the recommended maintenance plan (including the specific scheduled replacement of fans and power capacitors). Performing regular and pre-ventive maintenance not only keeps perfor-mance stable and extends the life of the equip-ment, but also decreases the risk of failure. In case these activities are not performed correct functioning of the equipment may be affected.
Maintenance inspections are essential to ensure a correct functionality and reliability of the UPS system.
During maintenance the field service engineer may carry out some or all of following checks:• Status and function check of UPS and batteries• UPS and batteries visual inspection (dust, me-
chanical damages, ...)• Visual inspection of screws and cable connec-
tions• Check of air ventilation and room temperature• Check the operation and function (commuta-
tions, remote monitoring and Signaling)• Current, voltage and frequency measurements• Measuring and registration of current load con-
ditions
• Checking of load sharing (only in parallel sys-tems)
• Battery voltage check• Battery discharge test• Check transfer of the load from UPS to mains
operation via static bypass• Unit cleaning• Preventive replacement of fans and capacitors
7.1.3 Deep battery testThe battery test takes approx. 3 minutes and should be performed only if:• There are no alarm conditions • The battery is fully charged • Mains is present.
The battery testing can be carried out inde-pendently of the operation mode (OFF-LINE or ON-LINE) and whether or not the load is con-nected. The battery test procedure can be per-formed from the UPS HMI, in the “User” setup menu or in the “Set-up User” menu of the Service Control Panel. The battery test can be planned and executed periodically once a month
7.1.4 Battery maintenance, disposal and re-cycling
BATTERY MAINTENANCE SHOULD BE CARRIED OUT BY A CERTIFIED SERVICE PARTNER.
TO ENSURE OPTIMUM OPERATION OF THE UPS SYSTEM AND CONTINUOUS AND EFFICIENT PROTECTION OF THE CONNECTED LOAD WE RECOMMEND CHECKING OF THE BATTERIES EVERY 12 MONTHS.
BATTERIES CONTAIN DANGEROUS SUBSTANCES THAT WILL HARM THE ENVIRONMENT IF DISPOSED OF. IF YOU CHANGE THE BATTERIES YOURSELF, CALL QUALIFIED ORGANIZATIONS FOR BATTERY DISPOSAL AND RECYCLING.
— 7.1 General maintenance
497 M A INTEN A N CE & TR O U B L E SH O OTI N G
7.2.1 For professional users in the European Union
THE CROSSED WHEELED BIN SYMBOL ON THE PRODUCT(S) AND / OR ACCOMPANYING DOCUMENTS MEANS THAT USED ELECTRICAL AND ELECTRONIC EQUIPMENT (WEEE) SHOULD NOT BE MIXED WITH GENERAL HOUSEHOLD WASTE.
IF YOU WISH TO DISPOSE OF ELECTRICAL AND ELECTRONIC EQUIPMENT (EEE), PLEASE CONTACT YOUR DEALER OR SUPPLIER FOR FURTHER INFORMATION.
CORRECT WASTE DISPOSAL OF THIS PRODUCT WILL HELP SAVE VALUABLE RESOURCES AND PREVENT ANY POTENTIAL NEGATIVE EFFECTS ON HUMAN HEALTH AND THE ENVIRONMENT, WHICH COULD OTHERWISE ARISE FROM INAPPROPRIATE WASTE HANDLING.
7.2.2 For disposal in countries outside of the European Union
THE CROSSED WHEELED BIN SYMBOL IS ONLY VALID IN THE EUROPEAN UNION (EU) MEANING THAT USED ELECTRICAL AND ELECTRONIC EQUIPMENT (WEEE) SHOULD NOT BE MIXED WITH GENERAL HOUSEHOLD
WASTE.
IF YOU WISH TO DISPOSE OF THIS PRODUCT PLEASE CONTACT YOUR LOCAL AUTHORITIES OR DEALER AND ASK FOR THE CORRECT METHOD OF DISPOSAL.
CORRECT WASTE DISPOSAL OF THIS PRODUCT WILL HELP SAVE VALUABLE RESOURCES AND PREVENT ANY POTENTIAL NEGATIVE EFFECTS ON HUMAN HEALTH AND THE ENVIRONMENT, WHICH COULD OTHERWISE ARISE FROM INAPPROPRIATE WASTE HANDLING
— 7.2 UPS disposal and recycling
— 7.3 Troubleshooting
7.3.1 AlarmsIn the event of an alarm condition the red LED-In- dicator “Alarm” and the acoustic alarm will turn on. In this case proceed as follows:• Silence the acoustic alarm by pressing the but-
ton "Reset".• Identify the cause of the alarm condition by
means of the EVENT LOG in the MAIN menu.• In case of doubts please contact the nearest
Service Center.• Fault identification and rectification informa-
tion is given on the following pages.
7.3.2 Menu, commands, event log and mea-surementsChapter 5 contains a detailed descriptionof the Menu, Commands, Event Log and Measure- ments that can be operated and displayed on the LCD. The List of Alarms and Messages are shown below.
50 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
7.3.3 Fault identification and rectification
The major alarm conditions that will be encountered are:
ALARM CONDITION MEANING SUGGESTED SOLUTION
MAINS RECT. FAULTMains power supply is outside prescribed tolerance.
The input power to UPS is too low or missing.If site power appears to be OK, check the input circuit breakers etc. supplying the UPS.
MAINS BYP FAULTMains power supply is outside prescribed tolerance.
The input power to UPS is too low or missing.If site power appears to be OK, check the input circuit breakers etc. supplying the UPS.
OUTPUT SHORTThere is a short circuit at the output of UPS (on load side).
Check all output connections and repair as required
OVERLOAD Load exceeds the UPS rated power.
Identify which piece of equipment is causing the overload and remove it from the UPS.Do not connect laser printers, photocopiers, electric heaters, kettles etc. to the UPS.
TEMPERATURE HIGHUPS temperature has exceeded the allowed value.
Check that the ambient temperature of the UPS is less than 40° C.If the ambient temperature is normal call the certified service center for assistance.
INV. PHASE FAULT Inverter is faulty.Call the certified service center for assistance.
SYNCHRON. FAULTThe inverter and mains are not synchronized.
The frequency of the input voltage to the UPS is outside operational limits and the UPS static bypass has been temporarily disabled.
BATTERY IN DISCHARGE Battery is near end of autonomy.Shutdown load connected to UPS before the UPS switches itself off to protect its batteries.
MANUAL BYP IS CLOSEDMaintenance Bypass closed. Load supplied by mains.
This alarm is only displayed if the UPS is on Maintenance Bypass.
In the case of alarms not included in the list above, please contact the nearest certified service center for assistance.
© Copyright 2018 ABB, All rights reserved. —
DPA
250
S4
50-2
50kW
—INSTALL ATION MANUAL
DPA 250 S4 UPS50-250 kW 380/400/415 V IEC
54 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
—8 Packing, transportation & storage
This chapter contains all the necessary information for the correct packing, transportation and un-packing of the UPS.
NOTE
WARNING
IF THE UPS IS NOT IMMEDIATELY INSTALLED THE FOLLOWING GUIDELINES MUST BE FOLLOWED:TRANSPORT:THE UPS CABINET CAN FALL OVER. USE THE SHIPPING BRACKETS ON THE REAR AND FRONT TO SECURE THE CABINETS. DO NOT TILT THEM MORE THAN 10° FROM VERTICAL, OTHERWISE CABINETS MAY TIP OVER. POTENTIAL DANGERS:- TILTING THE CABINET MIGHT DAMAGE THE SYSTEM AND THEREFORE SHOULD NO LONGER BE
CONNECTED TO THE MAINS.- WEIGHT OF THE UPS SYSTEM COULD CAUSE SERIOUS INJURIES TO PEOPLE OR ANYTHING IN THE
SURROUNDING AREA.STORAGE:- THE UPS SHOULD BE STORED IN THE ORIGINAL PACKING AND SHIPPING CARTON- THE RECOMMENDED STORING TEMPERATURE FOR THE UPS SYSTEM AND BATTERIES IS BETWEEN +20
°C AND +25°C. INDOOR AREA THAT IS RELATIVELY FREE OF CONDUCTIVE CONTAMINANTS- THE UPS SYSTEM AND THE BATTERY SETS MUST BE PROTECTED FROM HUMIDITY < 95% (NON-
CONDENSING)
The UPS and accessories are delivered on a spe- cifically designed pallet that is easy to move with a forklift or a pallet jack. Always keep the UPS in an upright position and do not drop the equip-ment.
Check before transporting the surface loading and use an adequate forklift to move the equip- ment to the final position.
For the weights refer to the technical data sheet.
WARNING
BE CAREFUL OF THE HEAVY WEIGHT OF THE UNIT
— 8.1 Packing & transportation
—8.1-1
—8.1-1: Forklift for transportation
55
Upon receipt of the goods, make sure that they correspond with the material indicated in the de-livery note.Carefully examine the packed unit(s) for any sign of physical damage. Two TiltWatch indicators (see figure 8.2-1) are placed on two sides of the packed unit, in a clearly visible position. They should both be intact and should not be red. If tipping has occurred the white arrow becomes red, as shown in figure 8.2-1 below.In the case of damaged unit(s) or even in the case of suspected damage (TiltWatch is red) inform immediately:
• The carrier• The manufacturer
— 8.2 Unpacking
NOTE
VISIBLE TRANSPORT DAMAGES MUST BE CLAIMED TO THE CARRIER IMMEDIATELY AFTER RECEIPT.
OTHER CLAIM FOR SHIPPING DAMAGE SHOULD ALSO BE FILED IMMEDIATELY AND THE CARRIER MUST BE INFORMED WITHIN 7 DAYS OF RECEIPT OF THE EQUIPMENT. THE MATERIALS USED FOR PACKING SHOULD BE STORED FOR FURTHER INVESTIGATION
—8.2-1: Tiltwatch
—8.2-1
8 PACK I N G , TR A NSP O RTATI O N & S TO R AG E
56 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
8.2.1 Standard package (film)
The major alarm conditions that will be encoun-tered are:
1. Perform the following steps to unpack the UPS equipment from the standard packaging:
2. Cut the two green straps that lock down the cardboard box. Remove the cardboard box by pulling up the top of it and then slide up the rest of the cardboard box starting from the bottom to the top.
3. Cut the tape from the four pieces of polysty-rene, and then remove them from the unit.
4. By paying extreme attention and without dam-
age the cabinet, unwrap the plastic film and re-move by pulling up the upper part of the bag that cover the unit, the edges are not pro-tected.
5. Fit the 4 adjustable feet (feet are in the acces-sory box, or at the bottom of the unit).
6. After having placed the UPS in its final posi- tion, dismantle the left and right socket and mount the front and back painted sockets.
7. Keep the packaging materials to ship the unit back
—8.2-1: Standard package unpacking sequence
—8.2-1
57
8.2.2 Sea freight cases (wooden box)
Perform the following steps to unpack the UPS equipment from the sea freight package:
1. Use a screwdriver or a pair of pliers to lift up all the tabs
3. Remove the front wall
2. Remove the lid
4. Remove the other front wall paying attention to the two side walls that could fall
—8.2.2-1: Sea freight cases unpacking sequence (Wooden box)—8.2.2-2: Sea freight cases unpacking sequence (Wooden box)
—8.2.2-1
—8.2.2-2
8 PACK I N G , TR A NSP O RTATI O N & S TO R AG E
58 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
5. Remove one of the side walls
7. Remove the corner brackets and the VCI bag
6. Remove the last side wall
8. Remove all screws from the supports and lift up the cabinet using a pallet truck
—8.2.2-3
—8.2.2-4
—8.2.2-3: Sea freight cases unpacking se-quence (Wooden box)—8.2.2-4: Sea freight cases unpacking se-quence (Wooden box)
59
8.3.1 UPSIf you plan to store the UPS prior to use, keep the UPS unpacked in a dry, clean and cool storage roomwith an ambient temperature between -25°C and +70°C and humidity of less than 95% non-condensing.
If the packing container is removed protect the UPS from dust.
NOTE
THE UPS SYSTEM, THE BATTERY CABINET AND THE BATTERIES ARE HEAVY AND MAY TIP DURING TRANSPORTATION CAUSING SERIOUS INJURY IF UNPACKING INSTRUCTIONS ARE NOT CLOSELY FOLLOWED.
8.3.2 BatteriesThe battery life depends very much on the ambient temperature. It is therefore important to follow the storage instructions/recommendations of the battery manufacturer. For long-term storage make sure that the battery is fully recharged every 6 months. Before and after storing, charge the battery.
Always store the batteries in a dry, clean, cool environment in their original packaging. If the packing container is removed protect the batteries from dust and humidity.
WARNING
SEALED BATTERIES MUST NEVER BE STORED IN A DISCHARGED OR PARTIALLY DISCHARGED STATE.EXTREME TEMPERATURE, UNDER- AND OVERCHARGE AND OVER DISCHARGE WILL DESTROY BATTERIES
— 8.3 Storage
—8.3.2-1: Batteries
WARNING
BE CAREFUL OF THE HEAVY WEIGHT OF THE BATTERIES
—8.3.2-1
8 PACK I N G , TR A NSP O RTATI O N & S TO R AG E
60 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
—9 Installation
9.1.1 Climatic conditionsAmbient temperature °C 0 to +40
Relative Humidity % < 95
Conditions of condensation No
Condition of wind-driven rain, snow, hail, etc. No
Conditions of water from sources other than rain No
Condition of icing No
The climate-controlling system could be periodically switched on or off but extremely high or low temperature shall be prevented.
9.1.2 Biological conditionsFlora (presence of mold, fungus) No
Fauna (presence of rodents and other animals) No
The location shall not have particular risks of biological attacks
9.1.3 Mechanical active substanceThe UPS shall not be placed in proximity to source of sand or dust.
9.1.4 Chemical active substanceLocation with normal level of contaminants experienced in urban areas over the whole area.
9.1.5 Mechanical conditionsThe UPS shall be placed in areas with insignificant vibration and shock
— 9.1 Environmental condition
The UPS is designed to be installed indoor, in temperature-controlled rooms. Heating, cooling, forced ventilation and humidification are used to maintain the conditions as shown in the next sub chapters:
619 I NS TA L L ATI O N
— 9.2 UPS location
The minimum needed clearances to allow for the correct airflow on the UPS system and to allow proper service and maintenance shall be respected as indicated below:
SINGLE DPA 250 S4 FRAMEUPS PARALLEL SYSTEM SIDE
BY SIDE INSTALLATION OR BATTERY CABINETS IN ROW.
A Back clearance for ventilation (forced air outlet)
200 mm 300 mm
B Front clearance needed to allow a correct door opening
1000 mm
C Maximum door opening angle 115°
D Top Clearance(Top clearance is only needed if there is no side clearance)
400 mm
—9.2-1: DPA 250 S4 clearances
—9.2-1
62 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
9.2.1 Battery cabinet location
In most cases the battery cabinet is positioned alongside the UPS cabinet (unless the UPS cabi-net requires side access) and takes advantage of the seam clearances. The minimum needed clear-ances of the battery cabinet depend on the de-sign of the cabinet (especially the openings). As VRLA batteries need natural ventilation, it is al-ways recommended to keep a certain clear- ance from the openings. How much that clearance needs to be highly depends on installation, good practice is to maintain a minimum of 100mm clearance at the walls with opening.
9.2.2 Fixing of the UPS to the building structure
WARNING
BE CAREFUL OF THE HEAVY WEIGHT OF THE BATTERIES
To fix the unit to the floor use the hole on each foot as shown on the drawing below. The quotes are in inches and [mm].
The fixing elements must be chosen in relation to the type of floor/support where the unit will be fixed.
—9.2.2-1: Fixing of the UPS to the building structure
—9.2.2-1
639 I NS TA L L ATI O N
— 9.3 Electrical installation
The customer has to supply the wiring to connect the UPS to the local power source. The installa-tion inspection and initial start-up of the UPS and extra battery cabinet must be carried out by a certified service engineers
DANGER
THE INSTRUCTIONS IN THIS USER MANUAL SHOULD ALWAYS BE FOLLOWED IN ORDER TO AVOID INJURIES FROM ELECTRICAL SHOCK
DANGER
ALL THE OPERATIONS DESCRIBED IN THIS MANUAL MUST BE PERFORMED BY CERTIFIED SERVICE ENGINEERS.DO NOT OPERATE IF WATER OR MOISTURE IS PRESENT.BY OPENING OR REMOVING THE UPS COVERS YOU RUN THE RISK OF EXPOSURE TO DANGEROUS VOLTAGES.PHYSICAL INJURY OR DEATH MAY FOLLOW, OR DAMAGE MAY OCCUR TO THE UPS OR THE LOAD EQUIPMENT IF THESE INSTRUCTIONS ARE IGNORED
NOTE
FOR A CORRECT WIRING CONNECTION, REFER TO THE CHAPTER “9.3.4 UPS TERMINAL SIZES”.
NOTE
THE FOLLOWING PICTURES ONLY REFER TO STANDARD CONFIGURATION
64 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
9.3.1 Single input feed - Terminals overview
X6N X2.1 X2.2 X2.3
X5.1
+ X5.2_
X3.1 X3.2 X3.3
X6N
X2.1 X2.2 X2.3OUTPUT CONNECTION
X5.1
+ X5.2_COMMONBATTERY
CONNECTION
X501.1
SEPARATE BATTERY CONNECTION
X501.2X502.1
X502.2X503.1
X503.2X504.1
X504.2X505.1
X505.2X506.1
X506.2
+ _ + _ + _ + _ + _ + _
—9.3.1-1: Single input feed - Terminal overview
—9.3.1-1
65
9.3.2 Dual input feed - Terminals overview—9.3.2-1: Dual input feed - Terminal overview
—9.3.2-1
X6N X2.1 X2.2 X2.3
X5.1
+ X5.2_
X6N
X2.1 X2.2 X2.3OUTPUT CONNECTION
X5.1
+ X5.2_COMMONBATTERY
CONNECTION
X501.1
SEPARATE BATTERY CONNECTION
X501.2X502.1
X502.2X503.1
X503.2X504.1
X504.2X505.1
X505.2X506.1
X506.2
+ _ + _ + _ + _ + _ + _
X3.1 X3.2 X3.3 X4.1 X4.2 X4.3
9 I NS TA L L ATI O N
66 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
9.3.3 Electrical protection and cable sizes
Cable sections are recommended according to IEC 60950-1. National and/or local regulations shall be considered to be in compliance with the regulations.
DANGER
TO REDUCE THE RISK OF FIRE, ONLY CONNECT TO A CIRCUIT PROVIDED WITH A MAXIMUM BRANCH CIRCUIT OVER- CURRENT PROTECTION IN ACCORDANCE WITH THE TABLE BELOW
9.3.3.1 Single input feed and common battery (default)—9.3.3.1-1: Single input feed and common battery block diagram
—9.3.3.1-1
67
UPS POWER RATING kW 50 100 150 200 250
Rectifier input fuse [Fuse A] gL or CB C curve, 3P
A 100 200 315 400 500
Rectifier input cable section (L1,L2,L3,N) [Cable A]
mm2 4x35 4x95 4x(2x50) 4x(2x95) 4x(2x120)
Rectifier input cable section (PE)
mm2 16 50 50 95 120
UPS output fuse gL or CB C curve, 4P [Fuse D]
A 100 200 315 400 500
Output cable section (L1,L2,L3,N) [Cable D]
mm2 4x35 4x95 4x(2x50) 4x(2x95) 4x(2x120)
Output cable section (PE)
mm2 16 50 50 95 120
Battery input fuse [Fuse E]
A 125 250 400 500 630
Battery cable section (+,-) [Cable E]
mm2 2x50 2x120 2x(2x95) 2x(2x120) 2x(2x150)
Battery PE cable section
mm2 25 70 95 120 150
Following external protection and cable sizes are recommended as per UPS power rating
9 I NS TA L L ATI O N
68 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
9.3.3.2 Single input feed and separate battery—9.3.3.2-1: Single inputfeed and separate battery block diagram
—9.3.3.2-1
69
UPS POWER RATING kW 50 100 150 200 250
Rectifier input fuse [Fuse A] gL or CB C curve, 3P
A 100 200 315 400 500
Rectifier input cable section (L1,L2,L3,N) [Cable A]
mm2 4x35 4x95 4x(2x50) 4x(2x95) 4x(2x120)
Rectifier input cable section (PE)
mm2 16 50 50 95 120
UPS output fuse gL or CB C curve, 4P [Fuse D]
A 100 200 315 400 500
Output cable section (L1,L2,L3,N) [Cable D]
mm2 4x35 4x95 4x(2x50) 4x(2x95) 4x(2x120)
Output cable section (PE)
mm2 16 50 50 95 120
Battery input fuse [Fuse E]
A 125 125 125 125 125
Battery cable section (+,-) [Cable E]
mm2 2x50 2x50 2x50 2x50 2x50
Battery PE cable section
mm2 25 25 25 25 25
Following external protection and cable sizes are recommended as per UPS power rating
9 I NS TA L L ATI O N
70 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
9.3.3.3 Dual input feed and common battery—9.3.3.3-1: Dual input feed and common battery block diagram
—9.3.3.3-1
71
UPS POWER RATING kW 50 100 150 200 250
Rectifier input fuse [Fuse A] gL or CB C curve, 3P
A 100 200 315 400 500
Rectifier input cable section (L1,L2,L3,N) [Cable A]
mm2 4x35 4x95 4x(2x50) 4x(2x95) 4x(2x120)
Rectifier input cable section (PE)
mm2 16 50 50 95 120
Bypass input fuse [Fuse B] gL or CB C curve, 3P
A 100 200 315 400 500
Bypass input cable section(L1,L2,L3,N) [Cable B]
mm2 4x35 4x95 4x(2x50) 4x(2x95) 4x(2x120)
Bypass input cable section (PE)
mm2 16 50 50 95 120
UPS output fuse gL or CB C curve, 4P [Fuse D]
A 100 200 315 400 500
Output cable section (L1,L2,L3,N) [Cable D]
mm2 4x35 4x95 4x(2x50) 4x(2x95) 4x(2x120)
Output cable section (PE)
mm2 16 50 50 95 120
Battery input fuse [Fuse E]
A 125 250 400 500 630
Battery cable section (+,-) [Cable E]
mm2 2x50 2x120 2x(2x95) 2x(2x120) 2x(2x150)
Battery PE cable section
mm2 25 70 95 120 150
Following external protection and cable sizes are recommended as per UPS power rating
9 I NS TA L L ATI O N
72 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
9.3.3.4 Dual input feed and separate battery—9.3.3.4-1: Dual input feed and separate battery block diagram
—9.3.3.4-1
73
UPS POWER RATING kW 50 100 150 200 250
Rectifier input fuse [Fuse A] gL or CB C curve, 3P
A 100 200 315 400 500
Rectifier input cable section (L1,L2,L3,N) [Cable A]
mm2 4X35 4x95 4x(2x50) 4x(2x95) 4x(2x120)
Rectifier input cable section (PE)
mm2 16 50 50 95 120
Bypass input fuse [Fuse B] gL or CB C curve, 3P
A 100 200 315 400 500
Bypass input cable section(L1,L2,L3,N) [Cable B]
mm2 4x35 4x95 4x(2x50) 4x(2x95) 4x(2x120)
Bypass input cable section (PE)
mm2 16 50 50 95 120
UPS output fuse gL or CB C curve, 4P [Fuse D]
A 100 200 315 400 500
Output cable section (L1,L2,L3,N) [Cable D]
mm2 4x35 4x95 4x(2x50) 4x(2x95) 4x(2x120)
Output cable section (PE)
mm2 16 50 50 95 120
Battery input fuse [Fuse E]
A 125 125 125 125 125
Battery cable section (+,-) [Cable E]
mm2 2x50 2x50 2x50 2x50 2x50
Battery PE cable section
mm2 25 25 25 25 25
Following external protection and cable sizes are recommended as per UPS power rating
9.3.4 UPS terminal sizes
LABEL CABLE SIZE TORQUE (Nm) TERMINALS DESCRIPTION
X3.1 M12 Bolt Terminal 50-75 Input Line L1
X3.2 M12 Bolt Terminal 50-75 Input Line L2
X3.3 M12Bolt Terminal 50-75 Input Line L3
X6 - N M12 Bolt Terminal 50-75 Neutral bar (N) [Common neutral]
X7 - PE M6 Bolt Terminal 6 Earth bar (PE) [Common earth]
X4.1 M12 Bolt Terminal 50-75 Bypass Line L1
X4.2 M12 Bolt Terminal 50-75 Bypass Line L2
X4.3 M12 Bolt Terminal 50-75 Bypass Line L3
X2.1 M12 Bolt Terminal 50-75 Output terminal, L1
X2.2 M12 Bolt Terminal 50-75 Output terminal, L2
X2.3 M12 Bolt Terminal 50-75 Output terminal, L3
X5.1: + M6 Bolt Terminal 50-75 Battery Terminal, +
X5.2: - M6 Bolt Terminal 50-75 Battery Terminal, -
9 I NS TA L L ATI O N
74 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
— 9.4 UPS connections
The customer has to supply the cables to connect the UPS to the local power grid source. To ensure cor-rect operation of the UPS and its ancillary equipment it is necessary to provide the mains cables with appropriate fuse protection. See chapter 9.3.3.
DANGER
INSTALLATION SHALL COMPLY WITH ALL APPLICABLE NATIONAL, STATE, AND LOCAL CODESTHE INSTRUCTIONS PROVIDED IN THIS USER MANUAL SHOULD ALWAYS BE FOLLOWED IN ORDER TO AVOID INJURIES FROM ELECTRICAL IMPACTSALL THE OPERATIONS IN THIS MANUAL MUST BE PERFORMED BY CERTIFIED ELECTRICIANS OR BY QUALIFIED INTERNAL PERSONNEL.DO NOT OPERATE IN CASE OF PRESENCE OF WATER OR MOISTURE.BY OPENING OR REMOVING THE UPS-COVERS YOU RUN THE RISK OF EXPOSURE TO DANGEROUS VOLTAGES PHYSICAL INJURY OR DEATH, OR DAMAGE MAY OCCUR TO THE UPS, OR TO THE LOAD EQUIPMENT IF THESE INSTRUCTIONS ARE IGNOREDTHE EQUIPMENT IS PROVIDED WITHOUT INPUT AND OUTPUT BREAKERS, A READILY ACCESSIBLE DISCONNECT DEVICE SHALL BE INCORPORATED EXTERNAL TO THE EQUIPMENT.
NOTE
EXTERNAL INPUT DISCONNECTION DEVICES MUST BE PROVIDED IN THE INSTALLATION TO PROPER OPERATE THE UPS
NOTE
POWER GRID REQUIREMENTS: A STANDARD UPS CAN CONNECT TO A THREE-PHASE, FIVE-WIRE (L1, L2, L3, N, PE) TT, TN-C, TN- S POWER DISTRIBUTION SYSTEMS (IEC60364-1).
INPUT NEUTRAL IS REQUIRED TO OPERATE THE RECTIFIER: In TN-S Systems, no 4-pole input switches or circuit breakers should be used. If you have to use a 4-pole switch for another reason, you have to be aware that, when open, the system - UPS and all downstream equipment - are floating against the PE.
UPS
0V 230V
NOTE
AVOID THE CONNECTION OF TWO SEPARATE DERIVED NEUTRAL IN THE DISTRIBUTION AS SHOWN IN THE PICTURE.
759 I NS TA L L ATI O N
9.4.1 UPS Input connections
NOTE
BEFORE PROCEEDING TO WIRE THE UPS, MAKE SURE THAT YOU HAVE READ AND UNDERSTOOD THE CHAPTER 9.4.
NOTE
TO ENSURE CORRECT OPERATION OF THE UPS, THE VOLTAGE TOTAL HARMONIC DISTORTION (THDu) OF THE MAINS SHALL NOT EXCEED 75% ACCORDING TO THE LEVELS OF THE STANDARD IEC 61000-2-2. IF THE INDICATED VALUES ARE EXCEEDED, PLEASE CONTACT THE MANUFACTURER
9.4.1.1 Mains supply and earth connection
To ensure protection of personnel during the installation of UPS make sure that the connections are performed under the following conditions:• No mains voltage is present• All Loads are shut down and disconnected• UPS is shut down and voltage-free• UPS Modules are fitted in correct position• Maintenance Bypass Q1 is open and in the OFF position• Remove terminal cover of the UPS• Connect first the ground-wire coming from the local power grid source to the terminal X7-PE (PE).
9.4.1.2 Single input feed
To achieve correct input cabling and protection, please refer to the chapter 9.3.For single input feed connect the mains input cable to UPS terminal block according to the following table:
MAINS INPUT CABLE UPS TERMINAL
Phase L1 X3.1:L1
Phase L2 X3.2:L2
Phase L3 X3.3:L3
NEUTRAL X6:N
GROUND (EARTH) X7:PE
There is a cable-fixing rail below the connection terminal of the UPS to ensure that the cables have been fastened properly. Keep the phase rotation in a clockwise direction.
9.4.1.3 Dual input feed
To achieve correct input cabling and protection, please refer to the chapter 9.3.For dual input feed remove the common input busbar and connect the rectifier mains and bypass mains input cables to UPS terminal block according to the following table:
UPS TERMINAL RECTIFIER
UPS TERMINAL BYPASS
X3.1:L1 X4.1:L1
X3.2:L2 X4.2:L2
X3.3:L3 X4.3:L3
X6:N X6:N
X7: PE
76 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
MAINS INPUT CABLE UPS TERMINAL BYPASS INPUT CABLE UPS TERMINAL BYPASS
Phase L1 X3.1:L1 Phase L1 X4:L1
Phase L2 X3.2:L2 Phase L2 X4:L2
Phase L3 X3.3:L3 Phase L3 X4:L3
Neutral X6:N Neutral N/N
GROUND (EARTH) X7:PE
There is a cable-fixing rail below the connection terminal of the UPS to ensure that the cables have been fastened properly. Keep the phase rotation in a clockwise direction
9.4.2 Output connections
NOTE
TO ENSURE CORRECT OPERATION OF THE UPS, THE LOADS CONNECTED TO THE OUTPUT MUST NOTEXCEED THE HARMONIC CURRENTS LEVELS PERMITTED IN IEC 61000-3-2 (load ≤ 16 A),IEC 61000-3-12 (16 A < load ≤ 75 A), or IEC/TS 61000-3-4 (load >75 A); IF THE INDICATED VALUES ARE EXCEEDED PLEASE CONTACT THE MANUFACTURER
NOTE
FOR ASYMMETRIC LOADS REQUIRING THE CIRCULATION OF A.D.C CURRENT HIGHER THEN 10% OF THE NOMINAL CURRENT, PLEASE CONTACT THE MANUFACTURER.
To ensure protection of the personnel during the installation of the UPS make sure that the connec-tions are performed under the following conditions:• No mains voltage is present• All Loads are shut down and disconnected• UPS is shut down and voltage-free• UPS Modules are fitted in correct position• Maintenance Bypass Q1 is open and in the OFF position • First of all connect the ground-wire to the terminal X7-PE (PE).
9.4.2.1 Load connection
To achieve correct output cabling and protection, please refer to chapter 9.3.The load cable should be connected to the UPS terminal block according to the following table:
OUTPUT CABLE UPS OUTPUT TERMINAL
Phase L1 X2.1:L1
Phase L2 X2.2:L2
Phase L3 X2.3:L3
NEUTRAL X6:N
GROUND (EARTH) X7:PE
77
—9.5-1: Communica-tion connection
—9.5-1
— 9.5 Parallel UPS connections
To ensure protection of personnel during the in-stallation of UPS make sure that the connections are performed under the following conditions:• No mains voltage is present• All Loads are shut down and disconnected• UPS units are shut down and voltage-free• UPS Modules are fitted in correct position• External Maintenance Bypass is open and in
the OFF position• Remove terminal cover of the UPS units• Connect the ground-wire coming from the lo-
cal power grid source to the terminal X7-PE (PE) of each UPS units in the parallel system.
9.5.1 Input & output connections
The input and output UPS connections in a paral-lel system shall be implemented as the stand-alone UPS connection described in chapter 9.4.
9.5.2 Communication connectionIf the UPS system consists of parallel UPS units, the installation of the “parallel cable” between them is required as follow:1. Start connecting one end of the parallel cable
to JD1 connector mounted on the first UPS unit2. Connect the other end of the parallel cable to
JD2 connector mounted on the second UPS unit.
3. If more UPS units are present on the parallel system, continue connecting the additional parallel cables on the same way until the last one.
4. The last parallel UPS unit must be connected to the first UPS unit (JD1 to JD2) to close the ring communication bus.
9.5.3 Interface set-up and configurationParallel board (NW40140) - DIP SW1:
SW1 1 SW1 2 SW1 3UPS Unit 1 ON ON ONOther UPS unit OFF ON ONStandalone UPS OFF OFF OFF
Customer interface (NW40085) - DIP SW1:
SW1 1 SW1 2UPS Unit 1 OFF OFFOther UPS unit OFF ONStandalone UPS OFF OFF
Jumpers: Parallel board (NW40140)*
Customer interface (NW40085)
JP1 ON NOT USEDJP2 NOT USED ONJP3 NOT USED NOT USEDJP4 NOT USED NOT USEDJP5 ON NOT USEDJP6 OFF NOT USEDJP7 NOT USED NOT USEDJP8 ON **ONJP9 ON NOT USEDJP10 ON ON (PIN 1-2)JP11 ON ON (PIN 1-2)JP12 ON NOT USED
*Jumper on CN59=ON ** With external output breaker JP8=OFF.
9 I NS TA L L ATI O N
78 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
—10 Commissioning
— 10.1 Start-up procedure
NOTE
PLEASE REFER TO CHAPTER "5.2.1.4-LED STATUS INDICATORS" FOR THE MEANING OF THE LED INDICATORS, COLOURS AND BEHAVIOUR
HE OPERATIONS DESCRIBED IN THIS CHAPTER MUST BE PERFORMED BY A SERVICE ENGINEER FROM THE MANUFACTURER OR BY AN AGENT CERTIFIED BY THE MANUFACTURER
10.1.1 UPS parallel installation situation before switching it on
1. Make sure the fuses for the supply of UPS-System in the input distribution board on site have been removed.
2. Make sure all the input, output and battery connections have been correctly performed.
3. Make sure all battery breakers in the UPS frame(s) and in the external battery cabinets are in the OFF position (Open).
4. Verify that the maintenance bypass switch(es).
Q1 (Optional) is/are in OFF position (Open).5. Verify that the output isolator/s Q2 is/are in
OFF position(Open).6. The general external output isolator (if any)
must be opened. No load must be connected to the parallel system output.
7. Verify that the DIP switch configuration on each frame in the parallel system is correct.• Dip switches on Parallel board/s
(see chapter 9.5)• Dip switches on Customer Interface
board/s (see chapter 9.5).
10.1.2 UPS input phase rotation check
1. Insert fuses in the customer distribution board:• Single input feed configuration
→ Insert input line fuses.• Dual input feed configuration
→ Insert Rectifier and Bypass line fuses.2. Check the input phase rotation and sequence
on each frame for both Rectifier and By-pass lines.
3. Remove the Rectifier fuses and, in case of dual input feed configuration, also the By-pass fuses in the customer distribution board.
10.1.3 Module installation and parameters check
1. Insert all modules in the frames.2. Fix all modules with the supplied screws (2
screws in each module).3. Insert Rectifier fuses line in customer distri-
bution board.
LED indicators status on all modules Display on all modules
LED INDICATION COLOR SINGLE INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load OFF
Battery Flashing Red
7910 CO M M ISSI O N I N G
LED indicators status on all modules Display on all modules
LED INDICATION COLOR DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Red
Load OFF
Battery Flashing Red
4. The 3 LEDs (Orange, Red and Green) present on all Parallel Interface boards (one in each frame) must be OFF.
5. The status of the green led on the Customer Interface board (one in each frame) changes according to the Multidrop feature setting.• Multidrop feature enabled:
The Green LED on the frame 1 flashes once per second. The Green LEDs in all remaining frames flash twice per second.
• Multidrop feature disabled: The Green LED on all frames flashes once per second.
6. Check if the operating parameters are cor-rectly set in all modules.
In particular verify:• The battery type, the number of blocks/
cells, and the autonomy time. Other parameters will be automatically set by the UPS (if no special battery floating or minimal voltage is required).
• Check if the batteries are connected as “Common” or “Separate” (Common Battery «Yes» or «No»).
• Verify the settings for output voltage and frequency.
• Correctly set the identification number of all frames and modules in the parallel installation (All modules on the same installation must have a univocal Id. number).
10.1.4 Q1 and Q2 feed-back check
1. If present, turn to ON and to OFF position (close and open) the maintenance bypass switch Q1 on all frames one at time and ver-ify that the messages “MAN BYP CLOSED” and “MAN BYP OPEN” is registered on the relative module(s) event log.
The “Load” led indicator becomes yellow when Q1 is in the ON position.
The relative symbol on the display changes as follow:
Q1 ON (Closed) Q1 OFF (Opened)
Display in case of single input feed configuration.
2. Turn to the ON and OFF position (close and open) the output isolator Q2 on all frames and verify that the relative symbol on the display changes as follows:
80 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
Q2 ON (Closed) Q2 OFF (Opened)
Display in case of single input feed configuration.
3. The message “UPS now is Master” is now present in the module event log.
4. By means of the ON/OFF button Load the module OFF (Confirm with ENTER when required).
LED indicators status: Module display:
LED INDICATION COLOR SINGLE INPUT FEED CONFIGURATION
Rectifier Green
Bypass Red (Green if single input feed)
Load OFF
Battery Flashing Red
5. Repeat the same series of operations with all other modules present in the parallel installa-tion. From the last one (below the one just tested) to the one in the lowest slot of the first frame).
Do not forget to check the status of LEDs and display indicators of each module.
10.1.6 Start-up procedure
1. With all modules in the parallel system Loaded OFF, switch to ON position (close) the output isolator Q2 of the last frame.
2. In case of “Dual input feed” configuration, insert the Bypass line fuses in the customer distribution board.
10.1.5 Modules check
1. Load-On to INVERTER mode the last module in the parallel installation (The module in the uppermost slot of the last frame):• Press the ON/OFF button until the confir-
mation window appears on the display.
• Confirm with ENTER button.2. Check if the starting sequence is correctly
executed and the UPS switches to INVERTER mode.
LED indicators status: Module display:
LED INDICATION COLOR SINGLE INPUT FEED CONFIGURATION
Rectifier Green
Bypass Red (Green if single input feed)
Load OFF
Battery Flashing Red
8110 CO M M ISSI O N I N G
3. Load-ON to INVERTER mode the last module in the parallel installation (The module in the uppermost slot of the last frame).
LED indicators status: Module display:
LED INDICATION COLOR SINGLE INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Green
Battery Flashing Red
4. As soon as the module is Loaded-ON, the Green led in the Parallel board inside this frame will lights up (This is now the “Master” frame).
5. Verify that the message “UPS now is Master” is now present in the module event log.
• This is now the “Master” module.6. Scroll through the module menu “Measure-
ments” and check to make sure that they are all correct.
7. Now executed the command “LOAD TO BY- PASS” from the module display.
LED indicators status: Module display:
LED INDICATION COLOR SINGLE INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Yellow
Battery Flashing Red
8. Now execute the command “LOAD TO IN-VERTER” from the module display.
9. Let the module operate in the INVERTER mode!
10. Load-ON to INVERTER mode the previous module in the frame (below the one just tested)
11. As soon as this module is Loaded-ON, the message “UPS now is Master” is recorded in its event log.• This is now the “Master” module.• The message “UPS now is slave” will be au-
tomatically recorded in the module previ-ously Loaded-ON (the one above this).
12. Check the module LED indicator status and the symbols on the display.
13. Execute now the command “LOAD TO BY-PASS” in this module.
14. The two modules must now switch together from INVERTER to STATIC BYPASS mode.
15. Switch back to INVERTER mode and verify again that both modules switch at the same time.
16. Let the two modules run in the INVERTER mode and repeat the same sequences of op-erations with all modules present in the frame (always from uppermost to lowest module position).
17. Move to the previous frame in the parallel in-stallation (if any) and close the relative out-put isolator Q2.
18. Repeat the same series of operations start-ing with the module in the uppermost posi-tion.
19. As soon as the first module present in the frame is Loaded-ON, the Green led of the rel-ative Parallel board will lights up (This is now the “Master” frame).
20. The Green led in the last frame will automati-cally switch OFF.
21. Verify always that the message “UPS now is Master” is recorded in the event log of the last module Loaded ON to INVERTER mode and the message “UPS now is slave” is re-corded in the previous ones.
82 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
Only one Master module must be present in the complete parallel system when all output isolators Q2 are in the ON position (closed)!
22. Repeat the same series of operations with all modules present in all frames of the parallel system.
23. At the end of the start-up procedure (all mod-ules loaded in INVERTER mode and all out-put switches Q2 in ON position), only the Green led present in the Parallel Interface board in-side the first frame (The Master one) is ON. All other Leds present in this and other paral-lel boards must be OFF.
10.1.7 Battery connection and check
1. Carefully check the battery polarity and volt-age.
2. Only if the battery polarity and voltage are correct insert the external battery fuses/turn to “ON” position the breakers.
3. Switch to ON position (close) the frame/s battery breakers related to the inserted modules.
LED indicators status on all modules Display on all modules
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Green
Battery Green
Wait up to 2 minutes until the battery is correctly recognized by all modules and the relative Led in-dicators all turn Green.
The modules are now recharging the batteries, the relative symbols on the display change as fol-lows (Battery filling from bottom to top):
4. If possible turn to OFF position (open) the general mains Rectifier Line isolator and verify that all modules in the parallel system start operating in battery mode.
LED indicators status on all modules Display on all modules
LED INDICATION COLOR DUAL INPUT FEED CONFIGURATION
Rectifier Red
Bypass Green (Red if single input feed)
Load Green
Battery Flashing green
The modules are now operating in battery mode to feed the load.The relative battery symbols on the display change as follows (Battery emptying from top to bottom).
8310 CO M M ISSI O N I N G
5. Turn the general mains Rectifier Line isolator to the ON position (closed) and verify that all modules in the parallel system switch back to normal operation (INVERTER mode)
10.1.8 Connecting the load1. Now transfer the load from INVERTER to
STATIC BYPASS mode by means of one mod- ule display or the general TFT display in- stalled on the frame.
Under the “COMMAND” menu select “LOAD TO BYPASS” (If required, enter the password if the command is performed through the TFT display).
2. If present, turn to the ON position (close) the maintenance bypass switch Q1 on all frames. (The messages “MAN BYP CLOSED” is regis-tered on all module(s) event log).
3. Turn to ON position (close) the system “Main External Output Isolator”.
The power is now supplied through the “Ex-ternal Maintenance Bypass”, the UPS/s “Inter-nal manual Bypass” and the modules “Static Bypass” lines!
4. Turn to the OFF position (open) the “External Maintenance Bypass” and lock it.
5. If the “External Maintenance Bypass” and the “Main External Output Isolator” are equipped
with auxiliary switch(es), connect as a feed-back their terminals to the Customer Inter face board/s NW40085 present in each frame.
In this way the Inverter on all modules pres-ent in the parallel installation will be locked while the External Maintenance Bypass is closed (Set to ON position).
6. If present, turn to OFF position (open) the maintenance bypass switch Q1 all the frames. (The messages “MAN BYP OPEN” is regis-tered on all module(s) event log).
7. Now transfer the load from STATIC BYPASS to INVERTER mode by means of one module dis-play or the general TFT display installed on the frame.
Under the “COMMAND” menu select “LOAD TO INVERTER” (If required, enter the pass- word if the command is performed through the TFT display).
The load is now protected by the 250 S4 UPS
84 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
—11 Shut-down procedure
— 11.1 Complete shut-down procedure
NOTE
PLEASE REFER TO CHAPTER "5.2.1.4-LED STATUS INDICATORS" FFOR THE MEANING OF THE LED INDICATORS, COLOURS AND BEHAVIOUR
HE OPERATIONS DESCRIBED IN THIS CHAPTER MUST BE PERFORMED BY A SERVICE ENGINEER OF THE MANUFACTURER OR BY AN AGENT CERTIFIED BY THE MANUFACTURER
The UPS may be shut down completely, if the load does not need input power for an extended period of time.It may be switched to maintenance BYPASS MODE for service or maintenance purposes or transferred to the OFF-LINE mode (ECO-mode) if the load does not need the highest degree of protection.
Only if there is no need to supply the load, the UPS system can be completely shut down.
The following procedures can only be executed after the load connected to the UPS has com-pletely been de-energized!
1. Verify that the loads are completely shut down and that there is no need for power supply to the load.
2. Load OFF all modules by means of the ON/ OFF buttons present on their control panels (Always confirm with “ENTER” when re-quired).
LED indicators status on all modules Display on all modules
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load OFF
Battery Flashing red
3. When all the modules present in the parallel installation are Loaded-OFF, turn to the OFF position (open) the Q2 output isolators on all frames.
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load OFF
Battery Flashing red
851 1 SH U T- D OW N PR O CED U R E
4. If present, turn to the OFF position (open) the parallel system “Main External Output Isolator” or open the external output fuses.
5. Turn to the OFF position (open) the battery breakers present on all frames and external battery cabinets or racks breakers or fuses.
6. Turn to the OFF position (open) the input mains switches/fuses (bypass and rectifier switches/fuses in case of dual input feed configuration) in the building distribution panel.
7. Wait at least five minutes until the modules AC and DC capacitors are completely discharged!
The DPA 250S4 is now voltage free
86 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
—12 Maintenance bypass operations
— 12.1 Load transfer from inverter mode to
maintenance bypass
NOTE
PLEASE REFER TO CHAPTER "5.2.1.4-LED STATUS INDICATORS" FOR THE MEANING OF THE LED INDICATORS, COLOURS AND BEHAVIOUR
HE OPERATIONS DESCRIBED IN THIS CHAPTER MUST BE PERFORMED BY A SERVICE ENGINEER OF THE MANUFACTURER OR BY AN AGENT CERTIFIED BY THE MANUFACTURER
In case of maintenance or service intervention, the load can be transferred to “MAINTENANCE BYPASS” (Operation usually required only in case of intervention to be performed on the frames).
Situation of UPS parallel system before starting the procedure:The load is protected by DPA 250 S4 UPS running in normal operation.All Modules operating on INVERTER mode!
LED indicators status on all modules Display on all modules
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Green
Battery Green
1. Transfer the load from INVERTER to STATIC BYPASS mode by means of one module dis-play or the general TFT display installed on the frame.
Under the “COMMAND” menu select “LOAD TO BYPASS” (If required, enter the password in case the command is performed through the TFT display).
2. Verify that all the modules in the parallel sys-tem are now operating in STATIC BYPASS mode.
871 2 M A I NTEN A N CE BY PA SS O PER ATI O NS
LED indicators status on all modules Display on all modules
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Yellow
Battery Green
3. If present, turn to the ON position (close) the maintenance bypass switch Q1 on all frames.
4. The message “MAN BYP CLOSED” will appear in the event log of all modules.
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Yellow
Battery Green
5. If the maintenance bypass switch Q1 is not installed in the frames, the load can be trans-ferred directly to “External Maintenance By-pass”. In this case turn to the ON position (close) the “External Maintenance Bypass” switch and lock it to this position.
6. Load OFF all modules by means of the ON/
OFF buttons present on their control panels (Always confirm with “ENTER” when re-quired).
7. The output isolator Q2 installed on all frames can be now opened (Turned to OFF position)
8. Turn to the OFF position (open) the battery breakers present on all frames and external battery cabinets or racks breakers or fuses
LED indicators status on all modules Display on all modules
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Yellow
Battery Flashing red
The load is NOT protected by the DPA 250S4 UPS
88 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
— 12.2 Load transfer from maintenance bypass to
inverter modeSituation of UPS parallel system before starting the procedure:
The load is supplied directly by Input Mains power (Via maintenance bypass switches Q1 if present on the frames or external maintenance bypass switch).
All modules are turned OFF
LED indicators status on all modules Display on all modules
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Yellow
Battery Flashing red
1. Be sure the maintenance bypass switches Q1 installed in all frames is in the ON position (closed)!
If not, perform this operation first of all.2. If in the ON position (closed), turn the exter-
nal bypass switch to the OFF position (open).3. Turn the output isolator QS installed on all
frames to the ON position (closed).
4. Load ON one by one all modules by means of the ON/OFF buttons present on their control panels (Always confirm with “ENTER” when required). All modules will now start operating in STATIC BYPASS mode (Inverter is locked).
5. Turn to ON position (close) the battery break-ers present on all frames and external battery cabinets or racks breakers or fuses (Wait 1, 2 minutes until the battery correctly are recog-nized by the modules).
LED indicators status on all modules Display on all modules
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Yellow
Battery Green
89
6. If present, turn to the OFF position (open) the maintenance bypass switch Q1 on all frames (The inverter is now unlocked on all modules)
7. The message “MAN BYP OPEN” will appear in the event log of all modules.
8. Transfer the load from STATIC BYPASS to INVERTER mode by means of one module
display or the general TFT display installed on the frame. Under the “COMMAND” menu select “LOAD TO INVERTER” (If required, enter the pass-word if the command is performed through the TFT display).
LED indicators status on all modules Display on all modules
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Green
Battery Green
The load is now supplied by the Inverter.
The load is now protected by the DPS 250s4 UPS.
1 2 M A I NTEN A N CE BY PA SS O PER ATI O NS
90 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
—13 Adding/replacing a UPS module
— 13.1 Single module system
NOTE
PLEASE REFER TO CHAPTER "5.2.1.4-LED STATUS INDICATORS" FOR THE MEANING OF THE LED INDICATORS, COLOURS AND BEHAVIOUR
THE OPERATIONS DESCRIBED IN THIS CHAPTER MUST BE PERFORMED BY A SERVICE ENGINEER OF THE MANUFACTURER OR BY AN AGENT CERTIFIED BY THE MANUFACTURER
There are two reasons for which removal or reinsertion of a module is required:• Module maintenance• Module failure
The procedures described on this chapter are almost the same in both cases. Follow carefully the pro-cedures to avoid any possible issue with the critical load.
In case the single operating module experiences a fault, the load will automatically be transferred to STATIC BYPASS mode and it will continue to be supplied by the mains power supply.
In this situation, the load must first be trans-ferred to maintenance bypass (Q1, if present) or to external maintenance bypass before the mod-ule can be removed.
13.1.1 Remove the module from the frame
Skip step 1 in case of module maintenance.1. Reset the alarm on the faulty module. The
acoustic signal will stop. If the alarm condition persists (Relative
ALARM LED indicator always RED) the module must be probably removed for analysis.
2. If the module already operates in STATIC BY-PASS mode, the maintenance bypass switch Q1 (if present) can be immediately turned to the ON position (closed).
If the maintenance bypass switch Q1 is not present, turn to the ON position (closed) the external maintenance bypass switch instead.
3. If the module still operates in INVERTER MODE, transfer first the load to STATIC BY- PASS mode.
Perform this operation by means of the module display or, if present, the general TFT display installed on the frame.
Under the “COMMAND” menu select “LOAD TO BYPASS” (If required, enter the password if the command is performed through the TFT display).
4. Turn to the ON position (closed) the mainte-nance bypass switch Q1 (if present) or turn to the ON position (closed) the external output bypass switch instead.
The message “MAN BYP CLOSED” will appear in the event log of the module as soon as the maintenance bypass switch Q1 is closed.
The load is now directly supplied by Mains and it is not protected.
LED indicators status on all modules Display on all modules
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Yellow
Battery Green
911 3 A D D I N G/R EPL ACI N G A U P S M O D U L E
5. Load OFF the module by means of the ON/OFF button present on its control panels (Al-ways confirm with “ENTER” when required).
6. Turn to OFF position (open) the module bat-tery breakers present on the frames and ex-
ternal battery cabinets or racks breakers or fuses.
7. Turn to OFF position (open) the output isola-tor Q2 installed on the frame.
LED indicators status on the module Display on the module
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Yellow
Battery Flashing red
8. Unscrew the two screws on the front side of the module fixing it to the UPS-frame.
9. Pull the module only partially horizontally by means of the 2 black handles until the rear connectors are disconnected.
10. Wait approx. 5 minutes before completely re-moving the module from the frame to be sure the AC and DC capacitors installed in it are completely discharged!
11. To extract the module completely, press down the top-left yellow tab (as shown in the figure here) and then draw the UPS module out by pulling it out horizontally.
NOTE
WE RECOMMEND 2 PEOPLE FOR PULLING OUT THE MODULE FROM THE FRAME.THE WEIGHT OF ONE MODULE IS APPROXIMATELY 66 KG
12. Insert now the UPS module or close the open-ing (UPS module compartment) with appro-priate protection cover immediately (Fix the cover with two screws).
92 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
13.1.2 Insert the module in the frame
The module must be previously set according to system personalization. Please contact your near-est service center for correct settings.
1. Remove UPS module compartment protec-tion cover by unscrewing the two fixing screws on the front.
2. Make sure that the “Battery breaker” of the slot where the module need to be inserted is turned to the OFF position (open).
3. Slide two thirds of the UPS module into the specific UPS compartment (make sure not to plug the UPS module into the rear connector).
Push UPS module to its final position and push firmly to assure good contact on the rear plugs.
NOTE
WE RECOMMEND 2 PEOPLE FOR INSERTION OF THE MODULE INTO THE FRAME. THE WEIGHT OF ONE MODULE IS APPROXIMATELY 66 KG
4. Fix the UPS module with the two screws on its front and tighten them with a torque of 6 Nm.
LED indicators status on the module Display on the module
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Yellow
Battery Flashing red
5. Check if the operating parameters are cor-rectly set in the module.• Battery type, the number of blocks/cells,
autonomy time, set as “Common” or “Sepa-rate” etc.
• Setting for output voltage and frequency.• Module and frame identification numbers.
6. Load ON the modules by means of the ON/OFF buttons present on their control panels (Always confirm with “ENTER” when required).
7. Check if the starting sequence is correctly ex-ecuted, with the module running in STATIC BYPASS mode at the end (Inverter is locked by Q1).
8. Turn to ON position (close) the module bat-tery breakers present on the frames and ex-ternal battery cabinets or racks breakers or fuses. Wait until the BATTERY LED turns green (ap-prox. 1 to 2 minutes), this means that the batteries are connected and are OK.
LED indicators status on the module Display on the module
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Yellow
Battery Green
9. Load OFF the modules by means of the ON/OFF buttons present on their control panels (Always confirm with “ENTER” when required).
10. Turn to ON position (close) the output isola-tor Q2 installed on the frame.
11. Load ON the modules by means of the ON/OFF buttons present on their control panels (Always confirm with “ENTER” when re-quired).
93
LED indicators status on the module Display on the module
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Yellow
Battery Green
12. Turn to OFF position (open) the maintenance bypass switch Q1 (if present) and turn to OFF position the external output bypass switch if previously turned to ON position (closed). The message “MAN BYP OPENED” will appear
in the event log of the module as soon as the maintenance bypass switch Q1 is turned to OFF position (opened). The load is now sup-plied by the module static bypass line.
LED indicators status on the module Display on the module
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Yellow
Battery Green
13. Transfer the load from STATIC BYPASS to INVERTER mode by means of one module display or the general TFT display installed on the frame.
LED indicators status on the module Display on the module
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Green
Battery Green
The load is now protected by the DPA 250S4 UPS.
1 3 A D D I N G/R EPL ACI N G A U P S M O D U L E
94 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
— 13.2 Redundant multi-module system
If in a redundant parallel system an UPS module is faulty, the load will continue to be protected by the remaining modules operating in an on-line-mode (INVERTER mode) and the faulty module can be replaced without having to transfer the
load to bypass!The same situation exist in the case of module maintenance, where the remaining modules oper-ating on-line-mode (INVERTER mode) will con-tinue to protect the load.
13.2.1 Remove the module from the frame
Skip step 1 and 2 in case of module maintenance.
1. Identify the faulty module with the alarm condition active.
2. Reset the alarm by pressing the BACK button on the module panel control.
The acoustic signal will stop. If the alarm condi- tions persists (relative ALARM LED in-dicator always RED) the module must be probably removed for analysis.
3. Load OFF the faulty module by means of the ON/OFF button present on its control panel (Confirm with “ENTER” when required). Perform the same operation in case of mod-ule maintenance operation.
Do not forget to always check that the re-maining modules on the parallel system can still supply the load! (Verify load measures on the operating modules).
4. Turn to OFF position (open) the relative mod-ule battery breakers present on the frames.
5. Unscrew the two screws on the front side of the module that fix it to the UPS-frame.
6. Pull the module only partly horizontally by means of the 2 black handles until the rear connectors are disconnected.
7. Wait approx. 5 minutes before completely re-moving the module from the frame to be sure the AC and DC capacitors installed in it are completely discharged.
8. To extract the module completely, press down the top left yellow tab (as shown in the figure) and then extract the UPS module by pulling it out horizontally.
NOTE
WE RECOMMEND 2 PEOPLE FOR PULLING OUT THE MODULE FROM THE FRAME.THE WEIGHT OF ONE MODULE IS APPROXIMATELY 66 KG
9. Insert new the UPS module or close the opening (UPS module compartment) with ap-propriate protection cover immediately (Fix the cover with two screws).
10. If the problem on the faulty module has caused a change in the complete parallel sys-tem operation mode (from INVERTER to BY- PASS mode or vice-versa) restore now the original situation. Transfer the load from STATIC BYPASS to IN-VERTER mode or vice-versa by means of one module display or the general TFT display in-stalled on the frame. Under the “COMMAND” menu select “LOAD TO BYPASS” (If required, enter the password in case the command is performed through the TFT display).
11. Verify that all remaining modules are operat-ing on the correct original mode.
951 3 A D D I N G/R EPL ACI N G A U P S M O D U L E
INVERTER MODE
LED indicators status on all operating modules Display on all operating modules
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Green
Battery Green
BYPASS MODE (ECO MODE)
LED indicators status on all operating modules Display on all operating modules
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Yellow
Battery Green
13.2.2 Insert the module in the frame
In a redundant parallel system one module can be reintroduced in its original location without af-fecting the normal system operation. The load will be protected by the other modules running in INVERTER or STATIC BYPASS mode.
The module must be previously set according to system personalization. Please contact your near-est service center for correct settings.
1. Remove UPS module compartment protec-tion cover by unscrewing the two fixing screws on the front.
2. Make sure that the “Battery breaker” of the slot where the module need to be inserted is turned to OFF position (opened).
3. Slide two thirds of UPS module into dedi-cated UPS compartment (make sure not to plug the UPS module into the rear connector). Push UPS module to its final position and push firmly to assure correct contact on the rear plugs.
NOTE
WE RECOMMEND 2 PEOPLE FOR INSERTION OF THE MODULE INTO THE FRAME. THE WEIGHT OF ONE MODULE IS APPROXIMATELY 66 KG
4. Fix the UPS module with the two screws at the front and tighten them with a torque of 6 Nm.
LED indicators status on the module Display on the module
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Yellow
Battery Flashing red
96 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
5. Verify that the operating parameters are cor-rectly set in the module.• Battery type, the number of blocks/cells,
autonomy time, set as “Common” or “Sepa-rate” etc.
• Setting for output voltage and frequency.• Module and frame identification numbers.
6. Load ON the module by means of the ON/ OFF button present on its control panels (Al-ways confirm with “ENTER” when required)
7. Check if the starting sequence is correctly ex-ecuted, with the module running according to the parallel system operation mode at the end (INVERTER or STATIC BYPASS mode).
8. Turn to ON position (close) the relative mod- ule battery breakers present on the frames. Wait until the BATTERY LED turns green (ap-prox. 1 or 2 minutes), this means that the bat-teries are connected and are ok.
The module is now protecting the load in par- allel with all other modules present in the system.
INVERTER MODE
LED indicators status on all operating modules Display on all operating modules
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Green
Battery Green
BYPASS MODE (ECO MODE)
LED indicators status on all operating modules Display on all operating modules
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Yellow
Battery Green
The load is now protected by the DPA 250 S4 UPS.
971 3 A D D I N G/R EPL ACI N G A U P S M O D U L E
— 13.3 Capacity multi-module system
If in the capacity parallel system a UPS module ex-periences a fault and there is not enough capacity left to protect the load by the remaining operat-ing UPS modules, the load will automatically be transferred to STATIC BYPASS and will continue to be supplied by the mains power supply.
The same situation exists when a module requires maintenance and the remaining ones still operat-ing in parallel cannot provide enough capacity to protect the load. In this case the load must be previously transferred manually to STATIC BY-PASS mode to be supplied by the mains power supply.
13.3.1 Remove the module from the frame
Skip step 1 and 2 in case of module maintenance.
1. Identify the faulty module with the alarm condition active.
2. Reset the alarm by pressing the BACK button on the module panel control.
The acoustic signal will stop. If the alarm con-ditions persist (relative ALARM LED indicator always RED) the module must be probably re-moved for analysis.
3. Verify that the parallel system is already op-erating in BYPASS mode and the load is sup-plied by the mains power.
If not, transfer the load from INVERTER to STATIC BYPASS mode by means of one mod- ule display or the general TFT display in- stalled on the frame.
Under the “COMMAND” menu select “LOAD TO BYPASS” (If required, enter the password in case the command is performed through the TFT display).
LED indicators status on all operating modules Display on all operating modules
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Yellow
Battery Green
4. If present, turn to ON position (closed) the maintenance bypass switch Q1 on all frame of the parallel system. If the maintenance bypass switch Q1 is not present, turn to ON position (closed) the ex-ternal maintenance bypass switch instead.
The message “MAN BYP CLOSED” will appear in the event log of all module as soon as one the maintenance bypass switch Q1 is closed.
LED indicators status on all operating modules Display on all operating modules
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Yellow
Battery Green
98 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
5. Load OFF the module by means of the ON/OFF button present on its control panels (Al-ways confirm with “ENTER” when required).
6. Turn to OFF position (open) the battery breakers of the slot where the faulty module/module that need maintenance is inserted.
LED indicators status on all modules Display on all modules
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Yellow
Battery Flashing red
7. Unscrew the two screws on the front of the module that fixes it to the UPS-frame.
8. Pull the module only partly horizontally using the 2 black handles until the rear connectors are disconnected.
9. Wait approx. 5 minutes before completely re-
moving the module from the frame to be sure the AC and DC capacitors installed in it are completely discharged!
10. If required, the remaining modules still oper-ating in STATIC BYPASS mode, can be now also loaded OFF until the removed module is reinserted in the parallel system.
In this case Load OFF one by one all modules by means of the ON/OFF button present on their control panels (Always confirm with “ENTER” when required).
11. To extract the module completely out, press down the top left yellow tab (as shown in the figure) and then extract the UPS module by pulling it out horizontally.
NOTE
WE RECOMMEND 2 PEOPLE FOR PULLING OUT THE MODULE FROM THE FRAME.THE WEIGHT OF ONE MODULE IS APPROXIMATELY 66 KG
The load is now directly supplied by mains and is NOT protected.
13.3.2 Insert the module in the frame
1. Remove UPS module compartment protec-tion cover by unscrewing the two fixing screws on the front.
2. Make sure that the “Battery breaker” of the slot where the module need to be inserted is turned to OFF position (opened).
3. Slide two thirds of UPS module into the spe-cific UPS compartment (make sure not to plug the UPS module into the rear connector). Push UPS module to its final position and
push firmly to assure good contact on the rear plugs
NOTE
WE RECOMMEND 2 PEOPLE FOR INSERT THE MODULE INTO THE FRAME.THE WEIGHT OF ONE MODULE IS APPROXIMATELY 66 KG
4. Fix the UPS module with the two screws on its front and tighten them with a torque of 6 Nm.
991 3 A D D I N G/R EPL ACI N G A U P S M O D U L E
LED indicators status on the module Display on the module
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Yellow
Battery Flashing red
5. Check if the operating parameters are cor-rectly set in the module.• Battery type, the number of blocks/cells,
autonomy time, set as “Common” or “Sep-arate” etc.
• Setting for output voltage and frequency.• Module and frame identification numbers.
6. Load ON the modules by means of the ON/OFF button present on its control panels (Al-ways confirm with “ENTER” when required).
7. Check if the starting sequence is correctly executed, with the module running in STATIC BYPASS mode at the end.
LED indicators status on the module Display on the module
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Yellow
Battery Flashing red
8. Turn to ON position (close) the relative mod-ule battery breakers present on the frames. Wait until the BATTERY LED turns green
(approx. 1, 2 minutes), this means that the batteries are connected and are ok.
LED indicators status on the module Display on the module
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Yellow
Battery Green
9. Load ON, if previously loaded OFF, all remain-ing modules in the parallel system by means of the ON/OFF button present on their con-trol panels (Always confirm with “ENTER” when required).
10. Check if the starting sequence is correctly ex-ecuted, with all modules running in STATIC BYPASS mode at the end.
100 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
11. Turn to OFF position (open) the maintenance bypass switch Q1 (if present) and turn to OFF position the external output bypass switch if previously turned to ON position (closed). The message “MAN BYP OPENED” will appear
in the event log of the modules as soon as all maintenance bypass switches Q1 are turned to OFF position (opened). The load is now supplied by the module static bypass line.
LED indicators status on all operating modules Display on all operating modules
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Yellow
Battery Green
12. Transfer the load from STATIC BYPASS to IN-VERTER mode by means of one module dis-play or the general TFT display installed on the frame.
LED indicators status on all operating modules Display on all operating modules
LED INDICATION COLOR SINGLE/DUAL INPUT FEED CONFIGURATION
Rectifier Green
Bypass Green
Load Green
Battery Green
The load is now protected by the DPA 250S4 UPS.
101
The REMOTE SHUTDOWN must use a normally closed contact, which opens to operate the remote shut down sequence.The remote shutdown on terminal port X3/1... X3/2 is located at the bottom-front of the frame on com-munication card with terminal blocks X3. See chapter 5.3 for details.In order to allow removal, maintenance or testing of any remote shut down facility without disturbing the normal operation of the UPS, it is recommended that a terminal block, with linking facilities, be in-stalled between the UPS and the stop button.
1. Use a screened cable with 1 pair (section of wires 0.5 mm2) and maximum length of 100 m.
2. Connect the cable as shown in figure. 14.1-1
X3/1X3/2
Terminal Block
Remote shutdown switch(N.C. = Normally closed)
UPSREMOTESHUTDOWN(X3)
—14.1-1: Remote shutdown
—14.1-1
—14 Operation procedures— 14.1 Remote shutdown
14 O PER ATI O N PR O CED U R E S
102 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
The Generator ON facility must use a normally open contact that closes to indicate that a generator is running and supplying input power to UPS. It is located at the bottom-front of frame on communica-tion card with terminal blocks X3/11 …X3/12. See chapter 5.3 for details.When used, this facility disables the UPS static bypass and prevents the UPS from transferring the load onto the generator power supply.
—14.2-1: Generator ON facilities
UPS GENERATOR PORT(X3)
X3/11X3/12
Generatoralarm panel
— 14.2 Generator ON facility
—14.2-1
103
— 14.3 Xtra VFI
14.3.1 Setup mode
In order to set up the Xtra VFI feature correctly, these two parameters must be known:• Highest Load Step (HLS)• Redundancy level
These parameters are explained in the next two sub-chapters.
Highest Load Step
The HLS parameter has to be inserted by your certified service personnel and can be adjusted at any time; access to the service-menu is required (service menu › settings › Xtra VFI). HLS should correspond to the highest load increase (load step) to be expected within the system in less than 50 ms, which the UPS system has to handle without any compromise.This parameter can be inserted as percentage of the total system capacity or as absolute value in kW or both (when both parameters are inserted, the system considers the worst case).
The factory default values for HLS are:
HLS in kW 0 kWHLS in % 0%
The factory default values for HLS are:
HLS in kW 0 – 3’000 kW (integer, positive)HLS in % 0 – 100 % (integer, positive)
In case the inserted value exceeds the physical possibilities of the system (e.g. HLS=1’200kW when the system capability is only 1’000kW) the UPS system applies the maximum possible value (in our example it would be 1’000kW).
Redundancy level
The redundancy level parameter has to be in-serted by the user (service menu › settings › Xtra VFI) and can be adjusted at any time. The redun-dancy level should correspond to the desired re-dundancy that the system should have. Typically, the redundancy level parameter=1, which means one additional module.
The factory default values redundancy level is
Redundancy level 0 modules
The possible values to insert are
Redundancy level 0 – 30 modules (integer, positive)
In case the inserted value exceeds the physical possibilities of the system (e.g. Redundancy level =24 when the system capability is only 20 mod-ules) the UPS system applies the maximum possi-ble value (in our example it would be 20 modules).
Start Xtra VFI
Once the two above parameters have been defined and set, Xtra VFI can be started simply by enabling it on the graphical display by your certified service personnel, access to the service-menu is required (service menu › settings › Xtra VFI) and can be disabled at any time.
14 O PER ATI O N PR O CED U R E S
104 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
14.3.2 Display menu
Navigation overview
The picture below shows all the views (screens) relevant for the Xtra VFI Feature (the display has a lot more screens that are now shown here, please see chapter 5.1 to see the entire menu).
The picture below also illustrates which button (icons) takes the user to a specific screen. The names given to each screen are used from here on.
—14.3.2-1: Naviga-tion overview
—14.3.2-1
0% 25% 50% 75% 100%
Load Active Standby
dd-mm-yy hh : mm : ss
Settings
UPS meas.
Measures
Battery
Xtra VFI
1/1
Inverters on 102
activeStatus
Inverters in standby 108
Total saved energy [kWh] 2
Saved energy [kWh] 1
Reset saved energy counter
of
of
dd-mm-yy hh : mm : ss
InverterRectifierLoad
L.2
L.1
dd-mm-yy hh : mm : ssP:01
01M 06
02 07
03 08
04 09
05 10
dd-mm-yy hh : mm : ss
Home screen
Xtra VFIstatus bar
Xtra VFI measures
Mimic diagram (module level)
Modulesselection
105
Xtra VFI measures screen
Figure 14.3.2-2 below, shows the Xtra VFI the measurement screen which is accessible via
Home screen by pressing the icon and then
—14.3.2-2: Xtra VFI measures screen
—14.3.2-2
This menu contains the following information/commands.
Status Shows the status of Xtra VFI. Refer to chapter "5.1.5.7 Xtra VFI"
Inverters on Shows the quantity of modules which are active (double-conversion).
Inverters standby Shows the quantity of modules which are in Standby.
Total saved energy [kWh] Indicates the saved energy since the first activation of Xtra VFI feature. Can be reset via service menu (PASSWORD NEEDED).
Saved energy [kWh] Indicates the saved energy since the last reset.
Can be reset by the button just below.
Reset saved energy counter Reset the saved energy counter
14 O PER ATI O N PR O CED U R E S
106 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
Xtra VFI status bar screen
Figure 14.3.2-3 below, shows the Xtra VFI status bar screen which is accessible via Xtra VFI mea-
—14.3.2-3: Xtra VFI status bar screen
—14.3.2-3
surements screen by pressing the icon or via Home screen by pressing the same icon.
This screen provides a graphical view of the sys-tem (live) by indicating the actual load applied to the UPS system (dark green) and the amount of
active and standby modules within the system (light green and light blue respectively). All indica-tions are expressed in % (of the system).
Module selection screen
Figure 14.3.2-4, shows the Modules selection screen which is accessible via any screen by
—14.3.2-4: Module selection screen
pressing the icon .
—14.3.2-4
This screen allows to enter the sub-menu of any module within the system simply by pressing one of the icons. By doing that, the user is accessing the module-level menus, which gives the possibil-
ity to see status and measurements of the se-lected module by starting at the Mimic diagram screen.
107
—15 Options
— 15.1 Network interface card (SNMP)
THE OPERATIONS DESCRIBED IN THIS CHAPTER MUST BE PERFORMED BY A SERVICE ENGINEER OF THE MANUFACTURER OR BY AN AGENT CERTIFIED BY THE MANUFACTURER
ABB modular system is provided with several fea- tures that allow for easy adaptation to the re-quired sites conditions. Following the “field in-stallable kits”:• Network interface cards (SNMP)• Elevation kit• Battery Temperature Sensor
Some of the features are design to be installed only during the assembling on the factory and for a safety reasons cannot be added on the field:• Manual Bypass
Please indicate these option features when plac-ing an order.
NOTE
ALL THE INPUT/OUTPUT PORTS ARE CLASS 2 (SELV CIRCUITS). PLEASE MAINTAIN SECURITY WHEN CONNECTING TO OTHER DEVICES.
ABB offers network inter-face cards to connect ABB UPS system to the net-work. The network interface card provides:• Remote monitoring via
Web• Environmental moni-
toring• Extensive alarm han-
dling and dispatching• Redundant UPS moni-
toring• Integration into net-
work or building management system
To install the SNMP card please follow the in-structions below:The Simple Network Management Protocol (SNMP) is a worldwide-standardized communication-protocol. It is used to monitor any device in the network via simple control language. The UPS-Management Software also provides its data in this SNMP format with its internal software agent. The operating system you are using must support the SNMP protocol.
We offer our software with SNMP functionality for Novell, OS/2, all Windows running on INTEL and ALPHA, DEC VMS, Apple.Two types of SNMP interfaces with identical func-tionality are available: an external SNMP-Adapter (Box) and an internal SNMP-Card. Both can man-age a parallel system (N modules) and return ei-ther global values - which are consistent for the whole parallel system - or specific values from the single modules.
—15.1-1: Customer interface slot SNMP
—15.1-1
External SNMP-Adapter
Internal SNMP-Card—15.1-2
—15.1-2: SNMP
The adapter may be configured via Telnet, HTTP (Web-Browser) or serial connection (Terminal). For normal operation at least one network con-nection (Ethernet) is required.
The SNMP adapter can be used, utilizing the RC-CMD send function, for an automatic network wide shut down or just for informing connected users. The shutdown procedure can be initiated on a low residual battery autonomy time (down-time) or by a countdown timer which is started at the beginning of the alarm. A shut down is there-fore possible without extra input from the opera-tor, and is fully software controlled.
1 5 O P TI O NS
108 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
The small (125x70 mm) External SNMP adapter comes with following interfaces:
1. RJ-45 connector for 10/100 Base-T (auto-switchable)
2. Serial Port for configuration (COM2) or optional ModBus interface.
3. Error/Link LED for UPS status4. Aux Port5. DIP Switch6. Serial Port to the UPS (COM1)7. DC Supply (9 VDC or 9-36 VDC supply,
depending on model)
The Internal SNMP-Card can be inserted into an appropriate extension slot of the PMC. This adapter communicates via the serial port of the UPS and makes a direct multiple server shut down possible without additional SNMP management software.
For detailed information please refer to the Soft-ware Manual provided with the PMC-Software CD ROM. RCCMD - Remote Console Command mod-ule for a multi-server shutdown. This standalone software module is designed to receive and exe-cute a command issued by a remote device. Thanks to RCCMD it is possible to execute a shut-down in a heterogeneous multi-platform net-work. The new release RCCMD2 is an application available for all Operating Systems, analogous to PMC-Software. Our SNMP Interfaces are compati-ble with RCCMD.
—15.1-3: CS141 advanced box
—15.1-3
—15.1-4: CS141 advanced slot
—15.1-4
15.1.1 CS121 basic
For interfacing the UPS with the network without the need for additional sensors or interfaces. Avail-able in slot and box formats.
Supports the following protocolsSNMP, Modbus TCP,HTTP ModBus TCP, Telnet FPT, SMTP (e-mail).
—15.1.1-1: CS141 advanced
—15.1.1-1
109
15.1.2 CS121 advanced
For interfacing UPS with the network and allowing users to connect additional sensors and I / O options either directly to the card or with sensor manager. Available in slot and box formats.
Supports the following protocolsHTTP, ModBus TCP ,SNMP Telnet FPT, SMTP (e-mail), ModBus RS-485
—15.1.2-1: CS141 advanced
—15.1.2-1
15.1.3 CS121 modbus
For interfacing UPS with the network and the ModBus RS485 with option to connect alarms buzzers or additional relay board. Available in slot and box formats.
Supports the following protocolsHTTP, ModBus TCP ,SNMP Telnet FPT, SMTP (e-mail), ModBus RS-485
—15.1.3-1: CS141 modbus
—15.1.3-1
1 5 O P TI O NS
110 D PA 2 5 0 S 4 5 0 - 2 5 0 K W O PER ATI N G M A N UA L
—15.1.4-1: SNMP board installation (1)
—15.1.4-1
—15.1.4-2
—15.1.4-2: SNMP board installation (2)
THE OPERATIONS DESCRIBED IN THIS CHAPTER MUST BE PERFORMED BY A SERVICE ENGINEER OF THE MANUFACTURER OR BY AN AGENT CERTIFIED BY THE MANUFACTURER NOTE
THIS KIT MUST BE INSTALLED ONLY ONCE THE UNIT IS ALREADY PLACED IN ITS FINAL POSITION.
—15.2-1: Elevation kit
—15.2-1
15.1.4 Installation of the SNMP board
1. Remove the 4 plastic lids from the unit2. Insert the SNMP card inside the slot
— 15.2 Elevation kit
111
— 15.3 Battery temperature sensor
15.3.1 Functions
The option Battery Temperature Sensor, if correctly installed has the following two functions:
1. Allows the battery temperature to be shown in the menu of the LCD display (see chapter 5.2.2.3)2. Allows the battery charger to automatically and continuously compensate the charging voltage ac-
cording to the values: 2.30 V/cell @15°C Linearly to... 2.23 V/cell @35°C.
15.3.2 Battery temperature probe installation
The sensor comes with a 1.8m cable, if a longer cable is needed, it can be extended up to 15m. First de-fine the position of the sensor, it is best to put it where the temperature gets higher (typically it’s on the top of a battery cabinet or UPS internal battery (or even battery room).Then, thread the wire by fixing it along the way and connect the two ends of the cable by plugging them into the customer interface (see chapter 5.3) on the pin X3/13 and X3/14. The polarity does not matter (not important which end is connected at X3/13 and which at X3/14).
UPS BATTERY PROBE PORT(X3)
X3/13X3/14
Batterytemperaturesensor
T
NOTE
THE BATTERY TEMPERATURE PROBE IS A CLASS 2 DEVICE (SELV CIRCUITS). PLEASE ROUTE THE CABLE TO MAINTAIN A MINIMUM OF 6MM FROM PRIMARY CIRCUITS.
NOTE
ONLY THE OPTIONAL BATTERY SENSOR FROM ABB IS COMPATIBLE
THE ADHESIVE OF THE BATTERY SENSOR IS SUITABLE FOR USE ON ALUMINUM, STAINLESS STEEL AND ENAMELED STEEL ONLY
THE EQUIPMENT IS PROVIDED WITHOUT INPUT AND OUTPUT BREAKERS, A READILY ACCESSIBLE DISCONNECT DEVICE SHALL BE INCORPORATED EXTERNAL TO THE EQUIPMENT
—15.3.2-1: Battery temperature probe
—15.3.2-1
1 5 O P TI O NS
—www.abb.com/[email protected]
© Copyright 2018 ABB. All rights reserved. Specifications subject to change without notice. —
D
PA 2
50 S
450
-250
kW