Date post: | 26-Nov-2023 |
Category: |
Documents |
Upload: | independent |
View: | 0 times |
Download: | 0 times |
Technical note
Cooling potential of ventilated PV facade and solar
air heaters combined with a desiccant
cooling machine
Li Meia,*, David Infieldb, Ursula Eickerc, Dennis Lovedaya,Volker Fuxc
aDepartment of Civil and Building Engineering, Loughborough University, Loughborough, LE11 3TU, UKbCREST, Loughborough University, Loughborough, LE11 3TU, UKcHochschule fur Technik Schellinstr 24, 70174 Stuttgart, Germany
Received 29 November 2004; accepted 12 June 2005
Available online 11 August 2005
Abstract
Thermal energy collected from a PV-solar air heating system is being used to provide cooling for
the Mataro Library, near Barcelona. The system is designed to utilise surplus heat available from the
ventilated PV facade and PV shed elements during the summer season to provide building cooling. A
desiccant cooling machine was installed on the library roof with an additional solar air collector and
connected to the existing ventilated PV facade and PV sheds. The desiccant cooling cycle is a novel
open heat driven system that can be used to condition the air supplied to the building interior. Cooling
power is supplied to the room space within the building by evaporative cooling of the fresh air supply,
and the solar heat from the PV-solar air heating system provides the necessary regeneration air
temperature for the desiccant machine. This paper describes the system and gives the main technical
details. The cooling performance of the solar powered desiccant cooling system is evaluated by the
detailed modelling of the complete cooling process. It is shown that air temperature level of the PV-
solar air heating system of 70 8C or more can be efficiently used to regenerate the sorption wheel in
the desiccant cooling machine. A solar fraction of 75% can be achieved by such an innovative system
and the average COP of the cooling machine over the summer season is approximate 0.518.
q 2005 Elsevier Ltd. All rights reserved.
Keywords: Solar energy; Ventilated PV facade/shed; Desiccant cooling; Energy balance calculation
Renewable Energy 31 (2006) 1265–1278
www.elsevier.com/locate/renene
0960-1481/$ - see front matter q 2005 Elsevier Ltd. All rights reserved.
doi:10.1016/j.renene.2005.06.013
* Corresponding author. Tel.: C44 1509223778; fax: 44 1509610031.
E-mail address: [email protected] (L. Mei).
L. Mei et al. / Renewable Energy 31 (2006) 1265–12781266
1. Introduction
A building integrated ventilated photovoltaic (PV) system is advantageous both from
electrical and thermal point of view. The air circulation behind the PV panel lowers the
temperature of PV module and thus improves their electrical performance. Furthermore, a
controlled air flow in the cavity between the PV panel and the surface behind leads to solar air
heating with the potential to be applied to building for winter preheating or summer cooling.
Over a number of years, the authors have investigated the thermal performance and the
application of the ventilated PV facade integrated to building in winter season [1–3].
Directly using of the warmed air from the PV facade for building heating is
environmentally sound. However, the thermal energy generated in the ventilated PV
facade is usually not used in summer when it is most abundant. It is also conceivable that
the PV facade structure might even add to the building’s cooling load. An attractive
solution to this problem is to use the heated air from the facade (which in summer is
unwanted and normally vented to the outside) to drive an adsorption cooling system for
buildings cooling in summer. The authors have recently completed an EU project which
concerned the ventilated PV-solar air heating system combining with a desiccant cooling
machine constructed and installed in the Mataro Library, near Barcelona.
The aim of this project is to design and implement an integrated solar heating and
cooling system using building integrated PV solar air heating components coupled to a
desiccant cooling system. The main scientific objective of the project is an integrated
energy analysis of such systems taking into account the thermal properties of the ventilated
PV facade and its impact on the heating and cooling loads of the building as well as the
generation of solar heated air and operation of the desiccant cooler. This has been done by
dynamic modelling and validation through an experimental evaluation of the system.
Several major innovations have been achieved in the project:
† The project proposed the first building integrated solar heating and cooling system in
Europe, using ventilated PV and solar air collectors for the heat production and
desiccant wheel technology for the solar driven cooling system
† An integrated energy analysis for the first time deliver validated results of the summer
performance of PV/solar air ventilated facades, consisting both the passive cooling
load caused the integrated components and their thermal energy production usable for
the active cooling system.
† Optimised control algorithms for solar powered desiccant systems have been
developed and tested. The control algorithm development and the integration into
standard building management system can enhance system performance and
significantly contribute to a cost reduction of such innovative cooling concepts.
2. The description of the system
The Mataro library building, near Barcelona, has a total surface area of 3200 m2,
distributed over three floor levels [4]. Both the south facade and the inclined sheds on
PV shed 1
PV shed 2
PV shed 3
PV shed 4
PV Facade
Air collector fieldmc, Tc
3000~9000m3
ms, Ts
mf, Tf
Fig. 1. Solar air system.
L. Mei et al. / Renewable Energy 31 (2006) 1265–1278 1267
the roof are equipped with ventilated PV modules (225 m2 on the south facade and a total
of 300 m2 on the roof). The original south PV facade is 6.5 m high, to which the 1.7 m high
air collectors have been added to boost the temperature levels of the ventilated PV system.
The ventilation channels of the four rows of the PV sheds on the roof (308 inclination) are
connected in parallel to the PV facade channel to supply a merged air volume to an
additional solar air collector field. This additional air collector field has the heating area of
105 m2 and is separated in three parallel strings with 35 m length and 95 mm channel
height. The further heated air from the additional air collectors is drawn to the desiccant
machine to regenerate the sorption wheel. The regeneration air can be controlled between
the maximum of 9000 m3/h and minimum of 3000 m3/h volume flow rate to keep a
necessary regeneration air temperature. The solar air system is shown in the Fig. 1
The desiccant cooling machine installed on the roof of the Mataro library is an open
heat driven cycle which comprises a sorption dehumidify wheel, a heat recovery wheel
and the humidifiers. Such system will collect outdoor air as the supply air and will first
dehumidify it with a silica-gel desiccant. By this dehumidification, the supply air warms
up and pre-cooling with the exhaust air by a heat exchanger is necessary. Thus, the
dehumidified supply air is cooled in a heat recovery wheel and further in an evaporative
humidifier. After the humidification of the supply air the maximum cooling effect is
limited by the maximum water content which is allowed to guarantee thermal comfort in
the building. The cooled supply air after humidification is passed to the indoor space to
satisfy the human environmental requirements. It is clear that the latent and sensible loads
of the room space are more efficiently handled in the desiccant cooling process than in
other cooling methods since components can be designed to handle these loads separately.
In the exhausting air stream, the silica-gel desiccant is regenerated by the solar heat air
from the PV-solar air collectors for releasing water moistures.
The desiccant wheel used in the system comprises a matrix containing parallel channels
which enables a large heat and mass transfer area to be maintained. The matrix is coated
with the silica-gel desiccants and has the 2100 mm of diameter, 360 mm of depth. The
wheel rotates slowly at the speed of 20 revolutions per hour. While, the heat recovery
wheel having the same diameter as the desiccant wheel rotates at 600 revolutions per hour
for the effective heat exchange. The volume flow rate in the supply and exhaust air streams
6 5
431
PVshed
PV facade
Air Collectors
Ambient air
Sorption wheel Recovery wheelHumidifier
2
78
Fig. 2. The simple scheme of the system.
L. Mei et al. / Renewable Energy 31 (2006) 1265–12781268
are controlled in 3000, 6000 and 12,000 m3/h for the different control strategies. The
simple scheme for this desiccant cooling system is shown in the Fig. 2.
For such a solar powered desiccant cooling system, the component models were
established and the simulation study of its performance was carried out. The thermal
building simulation tool of TRNSYS was used for simulate the desiccant cooling system
integrated with the Mataro Library building. When simulating the system operation
process including the control strategies, the energy balances for the building cooling were
yield.
3. Solar application
Since the desiccant cooling system was driven by solar air heat, the total useful heat
energy and the outlet air temperature of the ventilated PV facade and PVsheds as well as
the additionally installed solar air heater should be determined. As the air channels of the
PV facade and the PV sheds are parallel connected to supply the preheated air to
the additional air collectors, the temperature of the merged air is an important factor in the
solar cooling procedure. In general, a simplified Duffie’s solar air collector model [5] for
the both PV facade and PV sheds developed by the authors in the previously completed
project [1] was utilised to estimate the outlet air temperature of the PV facade and PV
sheds. This model is based on the standard test method for solar collectors. The
instantaneous thermal efficiencies of the PV facade and PV shed were given by:
hpf ZQu;pf
GTApf
Z 0:27K6:37Tin;pf KTa
GT
(1)
and
Tout;pf ZQu;pf
Cp _mf
CTin;pf (2)
L. Mei et al. / Renewable Energy 31 (2006) 1265–1278 1269
where Tin,pf(8C), Ta(8C) and GT (W/m2) obtained from the data logging system of the
Mataro Library are the inlet air temperature of the PV facade, the ambient air temperature
and the solar irradiance, respectively. The parameters of 0.27and 6.37 (W/Km2) were
estimated using the measured data, such as the air mass flow rate, the inlet and outlet air
temperatures of the PV channel, from Mataro Library data acquisition system during the
period 01/08/2000–06/08/2000, for 40 min periods around midday. Consequently, the
outlet air temperature of the PV facade, Tout,pf (8C)can be calculated by the inlet air
temperature, Tin,pf (8C), mass flow rate _mf (kg/s) and the total useful thermal energy Qu,
pf (W). In the Eqs. (1) and (2), the subscripts only stand for the PV facade. The same model
was used for the PV sheds and not repeated here. Then, it is clear to notice that the different
collecting areas collect the different useful thermal energy and cause the different outlet air
temperature for both the PV facade and PV sheds.
The performance characteristic of the additional solar air collectors (105 m2) was given
by the manufacture’s test data which can be expressed as:
hc
Qu;c
GTAZ 0:86K6:5
Tin;c KTa
GT
(3)
where, Tin,c (8C), the air collector inlet air temperature is the merged air temperature of the
PV facade and PV sheds. The regenerating air temperature to the desiccant cooling
machine is thus obtained by:
Tout;c ZQu;c
Cp _mc
CTin;c (4)
In order to maintain the regeneration air temperature at a significant level (above
70 8C), the ventilation air volume through the PV facade and PV sheds and the additional
solar air collectors should be controlled between 3000 and 9000 m3/h. In the simulation
model, a simple PI controller was designed for this purpose and implemented in the
simulation program. Both measured and simulated results show the total temperature
increase from ambient to the regeneration side of 35–40 K at high irradiance levels.
In the solar air system, the air volume through the PV facade and the PV sheds are
connected to the air collectors in parallel. The merged air temperature to the air collector
inlet thus approximates to the following relationship:
Tin;c Z_ms
_ms C _mf
Tout;ps C_mf
_ms C _mf
Tout;pf (5)
where, the outlet air temperatures of the PV facade and PV sheds, Tout,pf and Tout,ps are
inverse to the air mass flow rates of the PV facade and PV sheds, _mf and _ms. Thus, the solar
air collector inlet temperature, Tin;c, is not varied with the different ration of the _ms= _mf .
Furthermore, the regeneration solar energy delivered to the desiccant cooling machine is
not varied with the different ratio of the _ms= _mf .
L. Mei et al. / Renewable Energy 31 (2006) 1265–12781270
4. Desiccant cooling
The desiccant cooling machine including the sorption wheel, heat recovery wheel and
the humidifiers was modelled to simulate the summe_rtime psychrometric desiccant
processes and utilise hourly meteorological data to predict energy consumption
For the sorption wheel, the dimensionless effectiveness was used to characterise the
performance of the dehumidifier. In this study, the effectiveness of the dehumidifier was
assumed to be a constant. The humidity ratio and temperature of the air leaving sorption
wheel in the supply stream were determined by:
X2 Z X1KhdwðX1KXreÞ (6)
and
T2 Zh2K2500X2
1:004 C1:875X2
(7)
where, X (kg/kg), h (kJ/kg) and T (8C) are the humidity ratio, specific enthalpy and
temperature of air, respectively. The subscripts of 1,2 and so on in the following equations
indicate the positions shown in the Fig. 2. Xre (kg/kg) is the humidity ratio of the
regeneration air. h2 is determined by an approximate expression for the enthalpy of the
mixture air and explained in the Eq. (11).
In the heat recovery wheel, only the sensible heat exchange is in the process and the
humidity ratio is always constant. The temperature of the supply air stream leaving the
heat recovery wheel was:
T3 Z T2KhhwðT2KT6Þ (8)
For the humidifier, the enthalpy is approximately a constant in the evaporative cooling
process. The humidity ratio and temperature of the air leaving the humidifier can be
determined by:
X4 Z X3KhhdðXsKX5Þ (9)
and
T4 Zh4K2500X4
1:004 C1:875X4
(10)
where, Xs (kg/kg) is the humidity ratio at saturation state.
The modelling of condition along the entire process of desiccant cooling was carried
out for multiple psychrometric calculation. Within the calculations, the values of specific
enthalpy of the mixed humid air, h2 and h4, which are the energy content of humid air,
were calculated by an approximate expression of the sum of the enthalpy of dry air and the
enthalpy of water vapour related to the reference temperature 0 8C:
h2 Z 1:005T2 CX2ð2500 C1:875T2Þ h4 Z 1:005T4 CX4ð2500 C1:875T4Þ (11)
L. Mei et al. / Renewable Energy 31 (2006) 1265–1278 1271
The psychrometric equations from (6)–(11) were numerically solved to obtain the
steady state psychrometric values for each position in the desiccant cooling process.
In addition, the energy balance calculations based on the air temperature, humidity ratio
and specific enthalpy at the inlet of the desiccant system and the room space as well as the
solar air collector outlet were represented as:
† The cooling energy generated from the desiccant system:
Q_dsc Z _mdðh1Kh4ðWÞ (12)
† The sensible cooling load removed from the room:
Q_supply Z _mdCpðTroom KT4ÞðWÞ (13)
† The regeneration energy from solar heating system:
Q_reg Z _mcCpðTreg KT8ÞðWÞ (14)
† The auxiliary cooling energy supplied to the room:
Q_aux Z _mdCpðTroom K25:5 8CÞðWÞ (15)
† COP of the desiccant system:
COP Z COPQ_dsc
Q_reg(16)
† Solar fraction ZQ_supply
Q_load(17)
Where, _md (kg/s) is the supply air mass flow rate of the desiccant cooling machine.
5. Temperature and humidity assessment
The cooling process of the solar powered desiccant cooling system can be
illustrated by a typical steady state psychrometric process from the model simulation
results. For example, on 15th of June 2002 at 2:00pm, the warm moist air at 29.2 8C
and 0.011 kg/kg moisture content (relative humidity is about 38.9%) was vent through
the sorption wheel so that it came off at 41.3 8C and 0.0088 kg/kg moisture content
(relative humidity is about 17.7%). The supply air stream then past through the heat
recovery wheel and was sensible cooled to 24.6 8C. The cooled air then past through
an evaporative humidifier with an adiabatic efficiency of approximate 85%. In this
case, air can be supplied to the room space at 16.4 8C and 0.0108 kg/kg moisture
content (relative humidity is about 93%). On the return air side, air from the room
space at 25.5 8C and 0.0102 kg/kg moisture content (relative humidity is about 48%)
was drawn through the evaporative cooler so that it entered the thermal wheel at
approximate 18.6 8C and 0.011 kg/kg moisture content (relative humidity is about
91%). When the retune air stream past through the heat recovery wheel, it was
sensibly heated to approximate 35 8C and exhausted to the outside.
Table 1
Comparison of simulated and measured data for cooling process
Exterior
air
After
sorption
After
heat
recovery
After
humidifier
Return
air
After
return
humidifier
Air to
outside
Regener-
ation air
Simulated
8C 29.2 41.3 24.6 16.4 25.5 18.6 35 69.5
Kg/kg 0.011 0.0088 0.0068 0.0108 0.0102 0.011 0.011 –
RH 38.9% 17.7% – 93% 48% – –
Measured
8C 29.2 38.9 26.5 17.2 25.8 20.2 37.4 61.7
RH 37.6% 19.9% – 94.8% 50.5% – –
L. Mei et al. / Renewable Energy 31 (2006) 1265–12781272
On the regeneration air stream, the solar heated air at approximate 69.5 8C was vent
through the sorption wheel to regenerate the desiccants.
For validation purpose, a group of data measured from the Mataro library data
acquisition system on 5th of June 2002 at 2:00pm were recorded in the Table 1 and
compared with the simulation results given above. It can be seen that the simulated air
temperatures and humilities along the air flow stream were quite close to the measured
data. However, at some points, there were the reasonable differences between the
measured and simulated values. This perhaps related to the process modelling accuracy or
the system measuring errors. Then, in the simulation the desiccant system reached 16.4 8C
inlet air temperature, which is the design value.
In this study we also focused on the system dynamical simulation so that the solar
energy used and the cooling energy consumed for summer time can be analysed. As the
cooling machine relies purely on solar thermal heat from the ventilated PV-solar heat
system, the regeneration air temperature cannot be assumed to be constant. Thus, the
achievable solar fraction should be carefully analysed. So far a dynamical simulation
based on the component models described before and the hourly meteor weather data of
Barcelona has been carried out.
For the computer simulation, the sophisticated control strategies of the system were
simplified as the following supply/exhaust air volume control cascade:
† Supply air volume control: if the room temperature and the outside temperature are
below 24 8C and above 21 8C, the free ventilation operation will start—the supply and
exhaust air volume is 3000 m3/h. If the room temperature is above 24 8C, the desiccant
cooling starts operating and the supply/exhaust air volume is 6000 m3/h. If the room
temperature is higher than 24.5 8C, the supply and exhaust air volume will be gradually
increased to the maximum value, 12,000 m3/h.
† Auxiliary cooling supply control: if desiccant system cannot supply satisfactory
cooling energy to maintain the room temperature at 25.5 8C (or 26 8C), the auxiliary
cooling starts operation.
The supply and the exhaust air volume control cascade is illustrated in Fig. 3.
Aux. Cooler
3000m2/hr
6000m2/hr
12000m3/hr
Fig. 3. Supply and exhaust air volume control cascade.
L. Mei et al. / Renewable Energy 31 (2006) 1265–1278 1273
The complete solar powered cooling system was simulated for a volume flow on the
fresh air side of 6000–12,000 m3/h (the volume flow rate was depending on the control
strategies) and a variable volume flow of 3000–9000 m3/h on the regeneration side. The
input irradiance, temperature and humidity values are taken from the Meteonorm
database. From simulation, it can be seen that the temperature increase of PV-solar heater
can reach from the exterior to the regeneration of 35–40 K at high irradiance levels.
Approximate 70 8C of the regeneration air temperature can be obtained by a proper
controller to vary the volume flow on the regeneration air side between 3000 and
9000 m3/h. Fig. 4 shows this effect.
From Fig. 5, the room inlet air reaches 15–17 8C during cooling operation period in the
first ten days of July. On days with low irradiance levels (for example the 6th of July) the
regeneration air temperature is so low that no lower cooling effect is achieved. As ambient
air temperature levels are also rather low on that day, this should not present a problem.
During the free ventilation period (night), the room inlet air temperature is as the same as
the ambient air temperature. Depending on the control strategies, the room air temperature
can be controlled between 24 and 25.5 8C during the daytime. The maximum room
temperature in July is not higher than 25.6 8C.
Fig. 6 gives the absolute humidity of the ambient air, (supply air), room air and the air
after the sorption wheel for the first 10 days of July. For humidity simulation, there are no
control strategies implemented. So, the humidity level in the room only depends on the
ambient humidity ratio and the efficiencies of the dehumidifier and the humidifier.
However, the absolute humidity for the room inlet air is not allowed to be higher than
0
20
40
60
80
1 25 49 73 97 121 145 169 193 217 241First 10 days in July
Tem
per
atu
res
(C)
Tamb Treg
Fig. 4. Regeneration and ambient air temperatures with simulation time.
0
10
20
30
40
1 25 49 73 97 121 145 169 193 217 241First 10 days in July
Tem
per
atu
res
(C)
Tamb Troom Tsupply
Fig. 5. The room, ambient and supply air temperatures with simulation time.
0.000
0.005
0.010
0.015
0.020
1 25 49 73 97 121 145 169 193 217 241
First 10 days in July
Ab
solu
te h
um
idit
y(k
g/k
g)
Xamb Xroom Xsupply Xdhum
Fig. 6. Absolute humidity from simulation.
L. Mei et al. / Renewable Energy 31 (2006) 1265–12781274
0.01 kg/kg (RH 95%, 15 8C) when the desiccant cooling system operating. The effective
dehumidification of the sorption reaches about 0.005 kg/kg despite using the fresh air
humidifier.
6. Cooling load of inf/aud room
The solar powered desiccant cooling system in the Mataro library was designed to
supply the cooling energy to the large reading room—Inf/Aud room. The Inf/Aud room is
located in the west side and ground level of the Mataro library. The north wall, the large
part of south wall and the ground floor of the Inf/Aud room are adjoining to the soil. The
east wall and the ceiling are the interior partition. Thus, in the cooling load calculation for
the Inf/Aud room, solar radiation contributes the thermal flux only to the west wall, the
west window and the small part of the south wall.
As required in the cooling load calculation, the room dimension, the construction
material and the interior radiation of the Inf/Aud room are listed in Table 2.
Consequently, the shading influence, the adjoin soil temperature and the wind speed
were carefully considered and the Barcelona climatic data were used for the cooling load
calculation over 12 months period. The average cooling loads of the Inf/Aud room for the
August is around 9000 kWh.
Table 2
The thermal information of the Inf/Aud room
Wall description Construction Surface area U_value
(W/m2K)
West window Double glazing with 6 mm distance between two
4 mm glasses, 10% aluminium frame without any
thermal break
30.4 m!3.
2 mZ97.28 m2
4
West wall 0.25 m concrete insulation with 0.007 m steel
cover
30.4 m!1.
3 mZ39.52 m2
0.334
North wall Concrete wall completely adjoining soil (insulated) 15.5 m!4.
5 mZ69.75 m2
0.530
East wall Adiabatic two 0.02 m gypsum boards 30.4 m!4.
5 mZ136.8 m2
0.406
South wall 1 Adjoining soil, with internal common block and
face brick
15.5 m!3.
2 mZ49.6 m2
0.530
South wall 2 Not adjoining soil, with internal common block
and face brick
15.5 m!1.
3 mZ20.15 m2
0.334
Floor Concrete with insulation 30.4 m!15.
5 mZ417.2 m2
0.460
Ceiling Adiabatic 0.2 m lightweight concrete 30.4 m!15.
5 mZ417.2 m2
0.406
Room volume 30.4 m!15.
5 m!4.5 mZ2120 m3
Interior heat
radiation
40 persons, 6000 w lights and computers
L. Mei et al. / Renewable Energy 31 (2006) 1265–1278 1275
7. The energy balance
One of the important aims of the project was being capable of calculating the energy
balance of the system by the models simulation so that the valuations of system performance
and cost can be forecasted. Using the system models developed above, the energy balance has
been calculated relating to the Barcelona climatic data and the system control strategies.
For cooling purpose, the cooling energy generated by the desiccant cooling system was
calculated using the enthalpy difference between the ambient air and the room inlet air
from April to October. The total amount of 40,639 kWh cooling energy obtained refers to
the total enthalpy reduction from the ambient air to the room inlet air.
The regeneration energy for driving the desiccant cooling machine, for the period of
April to October, from ventilated PV-solar air heating system was calculated as 68,
829 kWh.
Table 3
The Cooling and regeneration power for summer season
April May June July Aug Sept Oct Total
Q_dsc (kWh) 501 2692 6562 11,831 11,395 6624 1034 40,639
Q_reg (kWh) 3356 7120 12,790 18,103 15,686 9832 1942 68,829
COP 0.149 0.378 0.513 0.654 0.726 0.674 0.533 0.518
Table 4
The supplied cooling energy to the room
April May June July Aug Sept Oct Total
Q_supply (kWh)
(at 3000 m3/h)
4285 3428 2098 1006 1214 1764 2810 16,605
Q_supply (kWh)
(at 6000 m3/h)
750 1234 2543 2592 2128 1981 753 11,981
Q_supply (kWh)
(at 6000–12,
000 m3/h)
344 1305 2026 3100 2473 1443 0 10,691
Q_supply (kWh)
(at 12,000 m3/h)
0 223 528 1739 1209 604 0 4303
Total Q_sup-
ply (kWh)
5379 6190 7195 8437 7024 5792 3563 43,580
L. Mei et al. / Renewable Energy 31 (2006) 1265–12781276
The coefficient of performance (COP), i.e. the ratio of produced cooling power to
required regeneration power, is on average 0.518 for this application. Table 3 shows the
monthly data of the regeneration energy, the desiccant cooling energy and the COP
calculated.
Using the room temperature calculated simultaneously for the aud/inf room, the cooling
energy effectively delivered to the room was obtained which depends on the enthalpy
difference between the room air and the room inlet air. The total cooling energy supplied
to the room from the desiccant cooling system is about 43,580 kWh.
Depending on the control strategies, both free ventilation and cooling ventilation were
applied to the system and three different ventilation air volumes were used. With respect to
the total cooling energy supplied to the aud/inf room, the free ventilation cooling energy
(3000 m3/h supply volume flow rate) is about 38%; the desiccant cooling energy supplied
at the volume flow rates of 6000 m3/h and between 6000 and 12,000 m3/h are 27 and 24%,
respectively; only 9% desiccant cooling energy is supplied to the room at 12,000 m3/h
volume flow rate. Table 4 shows the detailed monthly values.
With respect to the control strategies, the auxiliary cooling energy starts operating
when the room temperature is higher than 25.5 8C. Therefore, the auxiliary cooling energy
was calculated from the simulation, which can keep the room temperature at 25.5 8C
during the high cooling load periods. If considering the total amount of desiccant cooling
supply plus the auxiliary cooling energy as the total cooling demands for the aud/inf room,
the monthly solar fraction for desiccant cooling system was calculated and given
in Table 5. In average, 93% of the cooling demand for summer season can be covered by
Table 5
The solar fraction
April May June July Aug Sept Oct Total
Total Q_supply (kWh) 5379 6190 7195 8437 7024 5792 3563 43,580
Q_aux (kWh) 0 21 131 486 2099 605 0 3341
Q_supplyCQ_aux (kWh)
5379 6211 7326 8923 9123 6397 3563 46,921
Solar fraction 1.000 0.993 0.975 0.939 0.735 0.869 1.000 0.930
Table 6
Efficiency study
Efficiency Q_dsc (kWh) Q_supply (kWh) Q_aux (kWh)
Humidifier 0.8 11,831 8439 486
0.9 11,072 8673 355
0.95 10,609 8726 300
Dehumidifier 0.7 11,256 8395 533
0.8 11,831 8439 486
0.9 12,334 8481 448
Heat recovery 0.7 10,368 7979 780
0.8 11,831 8439 486
0.9 12,888 8711 278
L. Mei et al. / Renewable Energy 31 (2006) 1265–1278 1277
the solar powered cooling energy. At least, 73.5% of the cooling load can be removed by
the desiccant cooling in August.
8. Discussion
The results of the studies described above indicate that the amount of the cooling
energy supplied to the room space is sensible to the system parameters, such as the
efficiencies of the sorption wheel, heat recovery wheel and humidifier. If the efficiencies
for the three main components varied between 0.7 and 0.9 (in the above simulation, the
efficiencies are fixed as 0.8), the cooling energy supplied to the room also has G5.4%
change. This results to the changes of the auxiliary cooling supply amount and the solar
fraction value. The cooling energy generated from the desiccant system, the cooling
energy supplied to the room and the auxiliary cooling energy are given in Table 6 with the
different efficiencies for the simulation of the typical month of July.
In this study, the electrical consume of three ventilation fans was considered. The total
electric consumption of fans was calculated for the different three ventilation flow volume
rates. 13,557 kWh of electric energy could be used for summer season operation for the
desiccant cooling. This electrical consume should be added to the auxiliary cooling and the
solar fraction of the system should be analysed carefully.
It is necessary to indicate that the solar powered desiccant system can be operated in
heating mode for winter season. When operating in heating mode, the combination of solar
energy and recovered heat from the exhaust air stream appears to be capable of one-third
of the total heating energy required during the winter months. It also can be seen that most
of the auxiliary heating energy supplied to the room is during the no-solar period of the
day-evening and night.
9. Conclusion
In summary, building integrated ventilated photovoltaic facade and PV sheds can
significantly contribute to the thermal energy needs of buildings in summer season.
L. Mei et al. / Renewable Energy 31 (2006) 1265–12781278
The typical application of the thermal energy transmitted from PV facade and PV sheds is
to use it to drive a solar powered desiccant cooling system for buildings cooling. In this
paper, the establishment of the component models of a desiccant cooling system
regenerated by solar heat was described. The simulation study of the system performance
was carried out. When simulating the system operation process including the control
strategies, the energy balances for the building cooling were yield. The useful solar
thermal energy observed by ventilated PV-solar heating system and the effective cooling
energy generated from the desiccant cooling system have been calculated. With respect to
the regeneration energy from the solar air system, an average COP of 0.518 was obtained.
The supplied cooling energy from the desiccant cooling system for summer season were
estimated as 43,580 kWh which can achieve a solar fraction of 0.75 at least.
The results of the studies described in this paper demonstrate the potential of desiccant
cooling systems combined with ventilated PV facade/sheds. The results also confirmed
that the ventilated PV facade/sheds can produce the same order of magnitude of thermal
energy as the photovoltaic electric production for buildings heating and cooling.
Therefore, the concept of building integrating ventilated PV facade/sheds has the good
potential in the future.
References
[1] Infield D, Design, Study and Experimental Evaluation of an Integrated Solar Facade. E U project report
published by Europen Commision. 2000.
[2] Mei L, Infield D, Eicker U, Fux V. Thermal modelling of a building with an integrated ventilated pv facade.
Energy Building 2003;35(6):605–17.
[3] Eicker U, Fux V, Infield D, Mei L. Thermal performance of building integrated ventilated PV facade.
Proceedings of ISES Solar World Congress, Israel 1999.
[4] Lloret A, Aceves O, Sabata L, Andreu J, Merten J, Chantant M, Eicker U. Lessons learned in the electrical
system design, installation and operation of the Mataro public library. European photovoltaic solar energy
conference, Barcelona 1997 [pp. 1695–1664].
[5] Duffie JA, Beckman WA. Solar engineering of thermal processes. New York: Wiley; 1980.